Plan Review Notes
Plan Review Notes For Permit 03030015
Permit Number 03030015
Review Stop B
Sequence Number 1
Notes
Date Text
2003-04-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 MODEL A
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) SHEET S1, ROOF FRAMING PLAN.SUBMIT
 CALCULATIONS OR A SIGNED AND SEALED
 LETTER FROM THE ENGINEER TO VERIFY THAT
 THE EAVES UPLIFT LOAD OVER THE REAR
 COVERED PATIO IS ONLY 268 LB.
  
 2) SHEET S-1, ROOF FRAMING PLAN.ADD A
 KEY, FOR THE TRUSS ANCHOR REFERENCE
 ANNOTATION, TO CONFIRM IF1MEANS
 CONNECTOR MARK 1, AND IF 'U' IS THE
 DESIGN UPLIFT CAPACITY REQUIRED.WHAT
 IS THE VALUE STATED AS 'R', IS IT THE
 REQUIRED LATERAL LOAD CAPACITY (EITHER
 F1 OR F2)?
  
 3) SHEET S-2, CONNECTOR SCHEDULE.AMEND
 THE SCHEDULE TO INCLUDE THE UPLIFT AND
 THE LATERAL LOAD CAPACITY FOR THE
 SELECTED ANCHORS AND LUMBER GRADE.
  
 4) FBC TABLE 600THE GLASS BLOCK WINDOW
 IS ON THE PROPERTY LINE.AMEND THE
 PLANS TO SHOW THE REQUIREMENT FOR A ONE-
 HOUR FIRE-RATED ASSEMBLY.
  
 5) SHEET S3, PLYWOOD NAILING DETAIL.
 AMEND '10/32 CDX PLYWOOD' TO READ
 '19/32 CDX PLYWOOD'.
  
 6) PROVISO - ROOF TILE PRODUCT APPROVAL
 NOA# 99-1012.02 HAS EXPIRED.SUBMIT A
 CURRENT PRODUCT APPROVAL.
  
 7) PROVISO - OUTSWING STEEL DOUBLE DOOR
 PRODUCT APPROVAL NOA# 99-0311.03 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 8) PROVISO - ALUMINUM SLIDING GLASS DOOR
 PRODUCT APPROVAL NOA# 98-1228.01 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 9) PROVISO - ALUMINUM TUBE MULLION
 PRODUCT APPROVAL NOA# 99-0310.01 HAS
 EXPIRED.SUBMIT A CURRENT PRODUCT
 APPROVAL.
  
 10) PROVISO - SINGLE HUNG WINDOW PRODUCT
 APPROVAL NOA# 98-1222.02 HAS EXPIRED.
 SUBMIT A VALID PRODUCT APPROVAL.
  
 11) SHEET S-1, ROOF FRAMING PLAN.
 CONNECTOR MARK 5, SPECIFIED FOR THE
 EAVES OVER THE REAR COVERED PATIO, IS A
 SIMPSON TS9.THIS IS A TWIST STRAP FOR
 WOOD-TO-WOOD CONNECTIONS AND IS NOT
 SUITABLE FOR CONNECTION TO THE
 8F16-1B/1T FILLED CAVITY U-BEAM
 SPECIFIED FOR THIS LOCATION.AMEND THE
 REFERENCE.
  
 12) SHEET S-1, ROOF FRAMING PLAN.A
 CONNECTOR MARK 18 IS SPECIFIED IN FOUR
 LOCATIONS FOR THE ROOF OVER THE FRONT
 ENTRANCE PORCH.THERE IS NO MARK 18 ON
 THE CONNECTOR SCHEDULE (SHEET S2).
 AMEND THE REFERENCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS