2003-04-29 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| 1) SHEET S2, ROOF FRAMING PLAN.THE |
| GIRDER TRUSS ANCHOR MARK 3, ABOVE |
| BATH 2, HAS AN UPLIFT CAPACITY OF 1300# |
| (SEE SHEET S3, CONNECTORS SCHEDULE) |
| WHICH IS LESS THAN THE STATED UPLIFT |
| (U=1706#).AMEND THE PLANS. |
| |
| 2) SHEET S1, SECOND FLOOR FRAMING.THE |
| TWO FLOOR GIRDER ANCHORS MARK 6, |
| SPECIFIED AT THE WOOD POST BETWEEN THE |
| KITCHEN AND DINING ROOM, HAVE A COMBINED |
| UPLIFT CAPACITY OF 2970# (SEE SHEET S3, |
| CONNECTORS SCHEDULE) WHICH IS LESS THAN |
| THE STATED UPLIFT (U=3152#).AMEND THE |
| PLANS. |
| |
| 3) SHEET S3, CONNECTOR SCHEDULE. SIMPSON |
| HETAL 20 (CONNECTOR MARK 9) REQUIRES |
| 20-10D X 1-1/2" NAILS TO THE TRUSS AND |
| SIMPSON HGT 2 (CONNECTOR MARK 12) |
| REQUIRES 16D NAILS TO THE GIRDER.AMEND |
| THE SCHEDULE. |
| |
| 4) FBC 1007.3.1 STAIR TREADS AND RISERS. |
| ADD NOTES TO SHEET A1.01 TO STATE THE |
| RISER HEIGHT (MUST BE BETWEEN 7.5" AND |
| 7.75" WITH THE STATED 9" TREAD) AND TO |
| SPECIFY A NOSING.EVERY TREAD LESS THAN |
| 10" WIDE SHALL HAVE A NOSING OR |
| EFFECTIVE PROJECTION OF APPROX. 1" OVER |
| THE LEVEL IMMEDIATELY BELOW THAT TREAD. |
| |
| 5) FBC 607SHEET A0.01, NOTE 15 STATES |
| THAT THE CONSTRUCTION IS TYPE III.THE |
| CONSTRUCTION IS TYPE V.AMEND THE PLAN. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |