2003-04-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 1) SHEET S2, ROOF FRAMING PLAN.THE
 GIRDER TRUSS ANCHOR MARK 3, ABOVE
 BATH 2, HAS AN UPLIFT CAPACITY OF 1300#
 (SEE SHEET S3, CONNECTORS SCHEDULE)
 WHICH IS LESS THAN THE STATED UPLIFT
 (U=1706#).AMEND THE PLANS.
  
 2) SHEET S1, SECOND FLOOR FRAMING.THE
 TWO FLOOR GIRDER ANCHORS MARK 6,
 SPECIFIED AT THE WOOD POST BETWEEN THE
 KITCHEN AND DINING ROOM, HAVE A COMBINED
 UPLIFT CAPACITY OF 2970# (SEE SHEET S3,
 CONNECTORS SCHEDULE) WHICH IS LESS THAN
 THE STATED UPLIFT (U=3152#).AMEND THE
 PLANS.
  
 3) SHEET S3, CONNECTOR SCHEDULE. SIMPSON
 HETAL 20 (CONNECTOR MARK 9) REQUIRES
 20-10D X 1-1/2" NAILS TO THE TRUSS AND
 SIMPSON HGT 2 (CONNECTOR MARK 12)
 REQUIRES 16D NAILS TO THE GIRDER.AMEND
 THE SCHEDULE.
  
 4) FBC 1007.3.1 STAIR TREADS AND RISERS.
 ADD NOTES TO SHEET A1.01 TO STATE THE
 RISER HEIGHT (MUST BE BETWEEN 7.5" AND
 7.75" WITH THE STATED 9" TREAD) AND TO
 SPECIFY A NOSING.EVERY TREAD LESS THAN
 10" WIDE SHALL HAVE A NOSING OR
 EFFECTIVE PROJECTION OF APPROX. 1" OVER
 THE LEVEL IMMEDIATELY BELOW THAT TREAD.
  
 5) FBC 607SHEET A0.01, NOTE 15 STATES
 THAT THE CONSTRUCTION IS TYPE III.THE
 CONSTRUCTION IS TYPE V.AMEND THE PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO