2003-05-01 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 MODEL D (REVERSE)
  
 1) SHEET S-1, ROOF FRAMING PLAN.THE
 ROOF TRUSS ANCHOR AT THE WALL BETWEEN
 THE ATRIUM AND BEDROOM 2 IS CALLED UP AS
 DETAIL 5/S-4. SHEET S-4 HAS NO DETAIL 5.
 AMEND THE PLANS TO CORRELATE THE DETAILS
 IF THE REFERENCE ON THE ROOF FRAMING
 PLAN SHOULD BE TO DETAIL 4/S-4, AS DRAWN
 ON SHEET S-4, THEN THE COPIES OF
 SHEET S-1 MAY BE HAND-CORRECTED BY THE
 ENGINEER OF RECORD.SUCH A CORRECTION
 SHALL BE SIGNED AND DATED BY THE
 ENGINEER.
  
 2) SHEET S-1, ROOF FRAMING PLAN.THE
 HIP JACK ANCHOR AT THE PATIO COLUMN IS
 CALLED UP AS CONNECTOR MARK 8.THE
 CONNECTOR SCHEDULE ON S-2 DOES NOT
 INCLUDE A MARK 8.AMEND THE PLANS.
  
 3) NOTE: IF SHEET S-2 IS TO BE AMENDED,
 PLEASE CORRECT THE CONNECTOR MARK 4
 (SIMPSON MGT) ALLOWABLE UPLIFT TO 3965#
 (CURRENTLY SHOWN AS 4200#).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]