2003-12-17 00:00:00 | ****CORRECTIONS****** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEE CORRECTION LIST DATED 9/16/03. |
| THE PREVIOUS REVISION HAD BEEN ISSUED |
| WITH A PROVISO THAT ITEMS #6 AND #7 |
| AFFECTING SHEETS A4 AND A5 (CONNECTORS) |
| BE REVISED.THESE ITEMS WERE NOT |
| ADDRESSED PROPERLY. |
| |
| 2.)SEE ITEM #7, THERE ARE STILL |
| REFERENCES TO "LONG STRAPS".WHICH |
| STRAPS SHOULD BE USED?SPECIFY A |
| BRAND AND SPECIFIC CONNECTOR. |
| |
| 3.)SEE PREVIOUS LIST, ITEM #6.THE |
| CONNECTORS' DESIGN UPLIFT EXCEEDS THE |
| UPLIFT ALLOWED AS PER THE MANUFACTURER. |
| SEE ATTACHED.FOR USP, USE THE GREY BAR |
| SHOWING NO STRESS INCREASE FOR STEEL. |
| FOR MORE INFORMATION, SEE THE USP |
| CATALOG PP 6-7 IN REGARDS TO FBC1609.4. |
| |
| 4.)SEE PREVIOUS LIST, ITEM #6.YOU |
| HAVE SPECIFIED WOOD-TO-WOOD CONNECTORS |
| IN A WOOD-TO-MASONRY APPLICATION. EITHER |
| SPECIFY A DIFFERENT CONNECTOR, SUBMIT |
| ENGINEERING FROM THE MANUFACTURER |
| SHOWING THAT THIS CONNECTOR CAN BE |
| USED AND HAS BEEN TESTED IN THIS |
| APPLICATION, OR SUBMIT CALCULATIONS |
| SHOWING THAT THIS CONNECTOR CAN BE |
| USED IN THIS APPLICATION. |
| |
| 5.)ADDITIONAL FEES, $70 (REVISION FEE, |
| NO FREE RESUB FOR REVISIONS),BZ231391. |