Plan Review Notes
Plan Review Notes For Permit 03022335
Permit Number 03022335
Review Stop B
Sequence Number 5
Notes
Date Text
2003-12-17 00:00:00****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE CORRECTION LIST DATED 9/16/03.
 THE PREVIOUS REVISION HAD BEEN ISSUED
 WITH A PROVISO THAT ITEMS #6 AND #7
 AFFECTING SHEETS A4 AND A5 (CONNECTORS)
 BE REVISED.THESE ITEMS WERE NOT
 ADDRESSED PROPERLY.
  
 2.)SEE ITEM #7, THERE ARE STILL
 REFERENCES TO "LONG STRAPS".WHICH
 STRAPS SHOULD BE USED?SPECIFY A
 BRAND AND SPECIFIC CONNECTOR.
  
 3.)SEE PREVIOUS LIST, ITEM #6.THE
 CONNECTORS' DESIGN UPLIFT EXCEEDS THE
 UPLIFT ALLOWED AS PER THE MANUFACTURER.
 SEE ATTACHED.FOR USP, USE THE GREY BAR
 SHOWING NO STRESS INCREASE FOR STEEL.
 FOR MORE INFORMATION, SEE THE USP
 CATALOG PP 6-7 IN REGARDS TO FBC1609.4.
  
 4.)SEE PREVIOUS LIST, ITEM #6.YOU
 HAVE SPECIFIED WOOD-TO-WOOD CONNECTORS
 IN A WOOD-TO-MASONRY APPLICATION. EITHER
 SPECIFY A DIFFERENT CONNECTOR, SUBMIT
 ENGINEERING FROM THE MANUFACTURER
 SHOWING THAT THIS CONNECTOR CAN BE
 USED AND HAS BEEN TESTED IN THIS
 APPLICATION, OR SUBMIT CALCULATIONS
 SHOWING THAT THIS CONNECTOR CAN BE
 USED IN THIS APPLICATION.
  
 5.)ADDITIONAL FEES, $70 (REVISION FEE,
 NO FREE RESUB FOR REVISIONS),BZ231391.