Plan Review Notes
Plan Review Notes For Permit 03022335
Permit Number 03022335
Review Stop B
Sequence Number 3
Notes
Date Text
2003-09-15 00:00:00*****CORRECTIONS*****
 *****REVISION******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL FEES DUE, $36.26.
 BZ#230485 ATTACHED; PLEASE PAY AT
 CASHIER (INCREASED VALUE, RADON).
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)THE MINIMUM WALL INSULATION AS PER
 THE ENERGY CALCS SUBMITTED IS R5. REVISE
 ALL APPLICABLE DETAILS, INCLUDING
 WINDOW JAMB A2, STEMWALL SECTION A4,
 WALL SECTION A4.
  
 4.)ON THE WALL SECTION, A4, LOWEST
 BUILDING FLOOR ELEVATION SHALL BE A MIN.
 4" ABOVE FINISHED GRADE, CITY OF WEST
 PALM BEACH AMENDMENTS FBC1804.1.7.
  
 5.)WALL SECTION, A4, BOTTOM OF FOOTER
 IS REQUIRED TO BE A MINIMUM OF 12" BELOW
 FINISHED GRADE, FBC1804.1.3.
  
 6.)A5, USP TRUSS TIE DOWN SCHEDULE,
 UPLIFT ON SCHEDULE EXCEEDS MAXIMUM
 IN USP 2003 CATALOG FOR RT-T CONNECTORS.
 TARP HAS BEEN DISCONTINUED.RT-T IS
 A WOOD-TO-WOOD CONNECTOR AND CANNOT BE
 USED IN A WOOD-TO-MASONRY APPLICATION.
 THIS PERMIT WAS ISSUED WITH A PROVISO
 TO SUBMIT A NEW ATTACHMENT SCHEDULE.
 REVISE THE ATTACHMENT SCHEDULE, AND
 SPECIFY ALL ATTACHMENTS INCLUDING
 GIRDERS.
  
 7.)THE ROOF PLAN A5, AND THE KNEE WALL
 SECTION REFER TO A "LONG FLAT STRAP".
 SPECIFY WHICH STRAP IS TO BE USED.
  
 8.) THE PLANS SHOW EXISTING ROOF TRUSSES
 AND GIRDERS WHICH ARE TO BE RELOCATED.
 BE ADVISED THAT TRUSS ENGINEERING MUST
 BE PROVIDED AT THE TIME OF INSPECTION,
 INCLUDING THE EXISTING TRUSSES BEING
 RELOCATED.