2003-04-03 00:00:00**************** UNSAT **************
  
 1)NOTE : PLEASE SUBMIT AIC RATING FOR
 ALL NEW EQUIPMENT BEING INSTALLED. PER
 110-9/215-5
 MAINS/PANELS/BRKRS ARE ALL TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT.
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER 250-66.
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND PANEL.
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE CLARIFY ONLY ONE SMALL
 APPLIANCE CIRCUIT SHOWN ON PANEL SCHED?
 PLEASE NOTE, A MIN OF TWO IS REQ`D PER
 NEC 210-11C-1
  
 6)NOTE: PLEASE SEE FS/FAC 481/ 61G14
 PLEASENOTE, ALL CHANGES TO PLANS THAT
 ARE SIGNED AND SEALED BY AND ARCH, MUST
 HAVE "EACH" HANDWRITTEN CHANGE,
 INITIALED, DATED BY ARCH OF RECORD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]