Plan Review Notes For Permit 03022335 |
Permit Number |
03022335 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-04-03 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE : PLEASE SUBMIT AIC RATING FOR | | ALL NEW EQUIPMENT BEING INSTALLED. PER | | 110-9/215-5 | | MAINS/PANELS/BRKRS ARE ALL TO BE RATED | | FOR THE AVAILABLE FAULT CURRENT. | | | | 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | PER 250-66. | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | AND PANEL. | | | | 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTED CIRCUITS PER 210-12 ON PANEL | | SCHEDULE. | | | | 5)NOTE: PLEASE CLARIFY ONLY ONE SMALL | | APPLIANCE CIRCUIT SHOWN ON PANEL SCHED? | | PLEASE NOTE, A MIN OF TWO IS REQ`D PER | | NEC 210-11C-1 | | | | 6)NOTE: PLEASE SEE FS/FAC 481/ 61G14 | | PLEASENOTE, ALL CHANGES TO PLANS THAT | | ARE SIGNED AND SEALED BY AND ARCH, MUST | | HAVE "EACH" HANDWRITTEN CHANGE, | | INITIALED, DATED BY ARCH OF RECORD. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | [email protected] |
|