2003-04-18 00:00:00**********CORRECTIONS************
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.) BEFORE A PERMIT TO CONSTRUCT MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.THIS MAY BE DONE AFTER THE
 FINAL PLAN REVIEW, BUT BEFORE A PERMIT
 MAY BE ISSUED.
  
 3.)THE WINDOW JAMB AND DOOR JAMB
 DETAILS REFER TO AN ATTACHMENT SCHEDULE
 WHICH IS NOT ON THE PLAN.ALSO REFERS
 TO A DOOR ATTACHMENT WHICH IS
 INCOMPLETE.
  
 4.)FBC 1918.3.1, GABLE MUST BE
 STRUCTURALLY CONTINUOUS BETWEEN POINTS
 OF LATERAL SUPPORT.PLEASE ADDRESS.
  
 5.)NOTE #5, SHEET A-4, PLYWOOD
 SHEATHING NOTE DOES NOT MEET CITY OF
 WEST PALM BEACH REVISED TABLE 2306.1
 FASTENING SCHEDULE.PROVIDE A CORRECT
 ROOF SHEATHING FASTENING SCHEDULE (SEE
 ATTACHED).
  
 6.)THIS PROPERTY IS LOCATED IN THE A5
 FLOOD ZONE.CITY CODE SECTION 94-545
 REQUIRES THAT THE ADDITION HAVE A
 FINISHED FLOOR ELEVATION OF 6" ABOVE THE
 BASE FLOOD ELEVATION, WHICH IS 7'.THE
 FINISHED FLOOR IS REQUIRED TO BE AT 7'6"
 BUT THE PLAN SHOWS 7'.PLEASE REVISE.
  
 7.)FYI - HUGHES BRAND IS NO LONGER
 AVAILABLE.
  
 8.)SHOW HORIZONTAL REINFORCEMENT
 FOR COLUMNS IN THE WALL SECTION.
  
 9.)THE BOND BEAM IS REFERRED TO AS
 BOTH A SINGLE AND DOUBLE COURSE.PLEASE
 CLARIFY.
  
 10.)ON THE ENERGY CALC FORM, SIGN
 THE OWNER/AGENT LINE ON BOTH COPIES.
  
 11.)ADDITIONAL FEES REQUIRED.
  