2003-04-18 00:00:00 | **********CORRECTIONS************ |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE |
| A PERMIT CAN BE ISSUED. |
| |
| 2.) BEFORE A PERMIT TO CONSTRUCT MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION.THIS MAY BE DONE AFTER THE |
| FINAL PLAN REVIEW, BUT BEFORE A PERMIT |
| MAY BE ISSUED. |
| |
| 3.)THE WINDOW JAMB AND DOOR JAMB |
| DETAILS REFER TO AN ATTACHMENT SCHEDULE |
| WHICH IS NOT ON THE PLAN.ALSO REFERS |
| TO A DOOR ATTACHMENT WHICH IS |
| INCOMPLETE. |
| |
| 4.)FBC 1918.3.1, GABLE MUST BE |
| STRUCTURALLY CONTINUOUS BETWEEN POINTS |
| OF LATERAL SUPPORT.PLEASE ADDRESS. |
| |
| 5.)NOTE #5, SHEET A-4, PLYWOOD |
| SHEATHING NOTE DOES NOT MEET CITY OF |
| WEST PALM BEACH REVISED TABLE 2306.1 |
| FASTENING SCHEDULE.PROVIDE A CORRECT |
| ROOF SHEATHING FASTENING SCHEDULE (SEE |
| ATTACHED). |
| |
| 6.)THIS PROPERTY IS LOCATED IN THE A5 |
| FLOOD ZONE.CITY CODE SECTION 94-545 |
| REQUIRES THAT THE ADDITION HAVE A |
| FINISHED FLOOR ELEVATION OF 6" ABOVE THE |
| BASE FLOOD ELEVATION, WHICH IS 7'.THE |
| FINISHED FLOOR IS REQUIRED TO BE AT 7'6" |
| BUT THE PLAN SHOWS 7'.PLEASE REVISE. |
| |
| 7.)FYI - HUGHES BRAND IS NO LONGER |
| AVAILABLE. |
| |
| 8.)SHOW HORIZONTAL REINFORCEMENT |
| FOR COLUMNS IN THE WALL SECTION. |
| |
| 9.)THE BOND BEAM IS REFERRED TO AS |
| BOTH A SINGLE AND DOUBLE COURSE.PLEASE |
| CLARIFY. |
| |
| 10.)ON THE ENERGY CALC FORM, SIGN |
| THE OWNER/AGENT LINE ON BOTH COPIES. |
| |
| 11.)ADDITIONAL FEES REQUIRED. |
| |