Plan Review Notes For Permit 03022292 |
Permit Number |
03022292 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-13 00:00:00 | **************** UNSAT ************* | | | | 1)NOTE: PLEASE SET PLANS/SHEET SO PAGE | | CAN BE OPENED UP TO SEE LOAD CALCULATION | | -S. | | | | 2)NOTE: PLEASE SIZE SEC PER 310-15. | | | | 3)NOTE: UPON SIZING SEC, PLEASE SIZE | | GROUNDING ELECTRODE CONDUCTOR PER 250-66 | | | | 4)NOTE: PLEASE SEE SERVICE AMP/LOAD | | SHOWN @ 144? PLEASE SEE PANEL A/B LOADS. | | | | 5)NOTE: PLEASE LIST THE REQ`D BATH | | CIRCUIT(S) PER 210-52D/210-11-C-3 | | | | 6)NOTE: PLEASE SEE NOTE AT BOTTOM OF | | LOAD CALCS, NOTE MENTIONS SERVICE TO BE | | SIZED PER 220-17.PLEASE REMOVE, APPLIES | | TO APPLIANCES | | | | 7)NOTE: PLEASE SEE SCALE ON PLAN, SHOWS | | 1/4" =1'?? | | | | 8)NOTE: PLEASE SEE FEEDER SIZE FOR | | PANEL "A", 150ABRKR W/ 2/0`S, THIS IS | | PERMITTED, HOWEVER IF SHOWN ON PLAN, | | THEN IT MUST BE INSTALLED. PLEASE VERIFY | | WITH CONTRACTOR. | | | | 9)NOTE: PLEASE CORRELATE LOADS SHOWN ON | | PANEL "B" AND LOAD CALCUALTIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|