Plan Review Notes
Plan Review Notes For Permit 03022292
Permit Number 03022292
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-13 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SET PLANS/SHEET SO PAGE
 CAN BE OPENED UP TO SEE LOAD CALCULATION
 -S.
  
 2)NOTE: PLEASE SIZE SEC PER 310-15.
  
 3)NOTE: UPON SIZING SEC, PLEASE SIZE
 GROUNDING ELECTRODE CONDUCTOR PER 250-66
  
 4)NOTE: PLEASE SEE SERVICE AMP/LOAD
 SHOWN @ 144? PLEASE SEE PANEL A/B LOADS.
  
 5)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11-C-3
  
 6)NOTE: PLEASE SEE NOTE AT BOTTOM OF
 LOAD CALCS, NOTE MENTIONS SERVICE TO BE
 SIZED PER 220-17.PLEASE REMOVE, APPLIES
 TO APPLIANCES
  
 7)NOTE: PLEASE SEE SCALE ON PLAN, SHOWS
 1/4" =1'??
  
 8)NOTE: PLEASE SEE FEEDER SIZE FOR
 PANEL "A", 150ABRKR W/ 2/0`S, THIS IS
 PERMITTED, HOWEVER IF SHOWN ON PLAN,
 THEN IT MUST BE INSTALLED. PLEASE VERIFY
 WITH CONTRACTOR.
  
 9)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 PANEL "B" AND LOAD CALCUALTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372