2003-04-04 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| MODEL B REVERSE |
| |
| 1) SHEET S-1, ROOF FRAMING PLAN.NO |
| TRUSS ANCHORS ARE SPECIFIED ALONG THE |
| FAMILY ROOM WALL. |
| |
| 2) SHEET S-1, ROOF FRAMING PLAN.ADD A |
| KEY, FOR THE TRUSS ANCHOR REFERENCE |
| ANNOTATION, TO CONFIRM IF1MEANS |
| CONNECTOR MARK 1, AND IF 'U' IS THE |
| DESIGN UPLIFT CAPACITY REQUIRED.WHAT |
| IS THE VALUE STATED AS 'R', IS IT THE |
| REQUIRED LATERAL LOAD CAPACITY (EITHER |
| F1 OR F2)? |
| |
| 3) SHEET S-2, CONNECTOR SCHEDULE.AMEND |
| THE SCHEDULE TO INCLUDE THE UPLIFT AND |
| THE LATERAL LOAD CAPACITY FOR THE |
| SELECTED ANCHORS AND LUMBER GRADE. |
| |
| 4) FBC TABLE 600THE GLASS BLOCK WINDOW |
| IS ON THE PROPERTY LINE.AMEND THE |
| PLANS TO SHOW THE REQUIREMENT FOR A ONE- |
| HOUR FIRE-RATED ASSEMBLY. |
| |
| 5) SHEET S3, PLYWOOD NAILING DETAIL. |
| AMEND '10/32 CDX PLYWOOD' TO READ |
| '19/32 CDX PLYWOOD'. |
| |
| 6) PROVISO - ROOF TILE PRODUCT APPROVAL |
| NOA# 99-1012.02 HAS EXPIRED.SUBMIT A |
| CURRENT PRODUCT APPROVAL. |
| |
| 7) PROVISO - OUTSWING STEEL DOUBLE DOOR |
| PRODUCT APPROVAL NOA# 99-0311.03 HAS |
| EXPIRED.SUBMIT A CURRENT PRODUCT |
| APPROVAL. |
| |
| 8) PROVISO - ALUMINUM SLIDING GLASS DOOR |
| PRODUCT APPROVAL NOA# 98-1228.01 HAS |
| EXPIRED.SUBMIT A CURRENT PRODUCT |
| APPROVAL. |
| |
| 9) PROVISO - ALUMINUM TUBE MULLION |
| PRODUCT APPROVAL NOA# 99-0310.01 HAS |
| EXPIRED.SUBMIT A CURRENT PRODUCT |
| APPROVAL. |
| |
| 10) PROVISO - SINGLE HUNG WINDOW PRODUCT |
| APPROVAL NOA# 98-1222.02 HAS EXPIRED. |
| SUBMIT A VALID PRODUCT APPROVAL. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |