Plan Review Notes For Permit 03022281 |
Permit Number |
03022281 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-13 00:00:00 | ************* UNSAT ***************** | | | | 1)NOTE: PLEASE SIZE SEC PER 310-15 | | | | 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | PER 250-66, ONCE SEC`S ARE SIZE. | | | | 3)NOTE: PLEASE CORRELATE SERVICE AMP/ | | LOAD. 144A`S, SEE A`S ON A&B. | | | | 4)NOTE: PLEASE LIST THE REQ`D DEDICATED | | BATH CIRCUIT(S) PER 210-52D/210-11-C-3 | | | | 5)NOTE: PLEASE SEE NOTE AT THE BOTTOM | | OF LOAD CALCS. MENTIONS SERVICE TO BE | | SIZED @75% PER 220-17. PLEASE SEE 220-17 | | THIS IS FOR APPL LOADS ONLY. | | | | 7)NOTE: PLEASE CORRELATE SCALE SHOWN | | FOR PLANS SUBMITTED. 1/4"= 1' | | | | 8)NOTE: PLEASE SEE RECEPT SPACING, | | MISSING PER 210-52 | | | | 9)NOTE: PLEASE NOTE:FEEDER TO PANEL "A" | | IS SHOWN AT 2/0`S, THIS IS PERMITTED, | | HOWEVER IF SHOWN ON PLANS, THEN 2/0`S | | WILL BE REQ`D TO BE INSTALLED. PLEASE | | VERIFY THIS W/ CONTRACTOR/BLDER. | | | | 10)NOTE: PLEASE CORRELATE LOADS SHOWN | | ON PANEL "B" AND LOAD CALCULATIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|