Plan Review Notes
Plan Review Notes For Permit 03022281
Permit Number 03022281
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-13 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SIZE SEC PER 310-15
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER 250-66, ONCE SEC`S ARE SIZE.
  
 3)NOTE: PLEASE CORRELATE SERVICE AMP/
 LOAD. 144A`S, SEE A`S ON A&B.
  
 4)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH CIRCUIT(S) PER 210-52D/210-11-C-3
  
 5)NOTE: PLEASE SEE NOTE AT THE BOTTOM
 OF LOAD CALCS. MENTIONS SERVICE TO BE
 SIZED @75% PER 220-17. PLEASE SEE 220-17
 THIS IS FOR APPL LOADS ONLY.
  
 7)NOTE: PLEASE CORRELATE SCALE SHOWN
 FOR PLANS SUBMITTED. 1/4"= 1'
  
 8)NOTE: PLEASE SEE RECEPT SPACING,
 MISSING PER 210-52
  
 9)NOTE: PLEASE NOTE:FEEDER TO PANEL "A"
 IS SHOWN AT 2/0`S, THIS IS PERMITTED,
 HOWEVER IF SHOWN ON PLANS, THEN 2/0`S
 WILL BE REQ`D TO BE INSTALLED. PLEASE
 VERIFY THIS W/ CONTRACTOR/BLDER.
  
 10)NOTE: PLEASE CORRELATE LOADS SHOWN
 ON PANEL "B" AND LOAD CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  