Plan Review Notes For Permit 03022151 |
Permit Number |
03022151 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-06 00:00:00 | DRYER ROOM IS A CONFINED SPACE - TWO | | OPENINGS REQUIRED PER SECTION 304.3.1 | | OR ONE OPENING PER SECTION 304.3.2(2). | | REQUIRED. | | | | | | PER N. MELICK MANUFACTURE INFO | | NOT REQUIRED FOR 1 & 2 FAMILY HOMES. | | JULY 17, 2002 OFFICAL INTERPRETATION. | | THE FIELD INSPECTOR SHALL VERIFY THE | | INSTALLED EQUIPMENT INPUT DOES NOT EX- | | CEED THE PIPE SIZING. |
|