Plan Review Notes For Permit 03022093 |
Permit Number |
03022093 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-05 00:00:00 | ****************** UNSAT ************* | | | | 1)NOTE: PLEASESUBMIT OCP AND LOAD | | ON MDP THAT FEEDS TRANSFORMER. | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM ON | | E5.1, SHOWS TRANSFORMER BEING FLOOR | | MOUNTED AND ON PREVIOUS PAGE, SHOWS | | TRANSFORMER DIRECTLY IN FRONT OF | | ELECTRICAL PANELS. PLEASE SEE 110-26 | | FOR WORKING CLEARENCES. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|