Plan Review Notes For Permit 03021976 |
Permit Number |
03021976 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-05 00:00:00 | **********CORRECTIONS************ | | | | 1.)PLANS NOT SEALED.PLEASE SUBMIT | | NEW SEALED PLANS. | | | | 2.)SPAN INDICATED ON YOUR STRUCTURAL | | UPRIGHT SPACING CHART (7') DOES NOT | | MATCH THE PLAN GIVEN (8').PLEASE NOTE | | MAXIMUM UPRIGHT SPACING ON THE CHART. | | THE SPACING FOR 8' SPAN RANGES FROM 5'3" | | TO 6'4", DEPENDING ON OVERHANG.THE | | UPRIGHT SPACING SHOWN ON YOUR PLAN IS | | 7'.PLEASE CLARIFY. | | | | 3.)GIVE THE OVERHANG DIMENSION ON | | THE PLAN - SPACING OF UPRIGHTS VARIES | | ACCORDING TO OVERHANG SIZE. | | | | 4.)INDICATE THE PANEL/SKIN SIZE ON | | EITHER THE PLAN OR MARK ON THE CHART. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | LEA SMITH OR SAMANTHA THYNG | | 561-659-8096, EXTENSION 8340 |
|