2003-03-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} NOTE# 3(ELECTRICAL) ON SHEET "A-1"
 REFERENCES # 12"TW"WIRE,BUT THE PANEL
 SCHEDULE HAS #14 WIRE IN SOME
 INSTANCES.PLEASE CLARIFY AND WAS THE
 INDICATED "TW" DESIGNATION FOR THE
 INSULATION TYPE INTENDED?
  
 2} WHERE IS THE NEW ELECTRICAL PANEL IN
 THE GARAGE BEING FED FROM? PANEL "A"
 DOES NOT SHOW AN OCP FOR THAT PANEL.
  
 3} PANEL "C" MUST COMPLY WITH ARTICLES
 250-32 & 225-31.
  
 4} BATH CIRCUITS MUST COMPLY WITH
 210-11(C)(3).
  
 5} KITCHEN COUNTERTOP RECEPTACLES MUST
 COMPLY WITH 210-52(C)(1).
  
 6} RECEPTACLES TO COMPLY WITH 210-8
 WHERE APPLICABLE,PLEASE INDICATE THE
 SAME ON THE PLANS.
  
 7} PLEASE COMPLY WITH
 210-70(A)(2),EXTERIOR DOOR EGRESS LIGHT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659 8096 EXT.8392