Plan Review Notes
Plan Review Notes For Permit 03021580
Permit Number 03021580
Review Stop B
Sequence Number 1
Notes
Date Text
2003-03-26 00:00:00**********CORRECTIONS************
  
 PLEASE NOTE FBC 3401.7.1 AND 3401.7.2
  
 1.)IMPACT FEES WERE FOR 386 SQUARE
 FEET, CABANA ONLY.IMPACT FEES MUST
 BE PAID ON THE NEW HOUSE ADDITION.
 THE ACTUAL PERMIT PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.PLEASE CALL 561-233-5025
 FOR MORE INFORMATION.
  
 2.)AREA TABULATION IS NOT CORRECT.
 PLEASE REVISE.AREA OF THE BAY WINDOW
 SHOULD ALSO BE INCLUDED.IF THE PATIO
 WAS PREVIOUSLY INDOOR AIR CONDITIONED
 SPACE, THIS REDUCTION SHOULD ALSO BE
 REFLECTED IN THE AREA TABULATIONS.
 IMPACT FEES WILL BE PAID ON ADDITIONAL
 LIVING AREA INCREASE.
  
 3.)SEPARATE ENERGY CALCS REQUIRED FOR
 THE CABANA.
  
 4.)PER FBC 104.2.1.1, PROVIDE ROOF
 FLASHING REQUIREMENTS & WIND RESISTANCE
 RATINGS THAT ARE REQUIRED TO BE
 INSTALLED.
  
 5.)A 2X4 SKYLIGHT IS SHOWN HIGHLIGHTED
 ON SHEET A1.IF THIS IS A PROPOSED
 SKYLIGHT, SUBMIT PRODUCT APPROVALS.IF
 THIS IS EXISTING, INDICATE ON THE PLAN.
  
 6.)PROVIDE PRODUCT APPROVALS FOR
 THE MULLS FOR WINDOW 8 AND FOR THE
 45 DEGREE BAY MULLS.
  
 7.)PROVIDE PRODUCT APPROVALS FOR
 THE EXTERIOR DOORS.
  
 8.)PROVIDE PRODUCT APPROVALS FOR
 THE CASEMENT WINDOWS #12.
  
 9.)PLEASE DATE THE ARCHITECTURAL
 SEAL AS PER FLORIDA STATUTE 61G1-16.003.
  
 10.) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 11.)ONE ACCESSIBLE BATHROOM REQUIRED
 FOR ALL RESIDENCES PER FBC 11-11 (1).
  
 12.)1403.1.6 IN ORDER TO PROVIDE FOR
 INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVER-
 INGS AND FINAL EARTH GRADE ON THE
 EXTERIOR OF A BUILDING SHALL NOT BE LESS
 THAN 6 INCHES.PLEASE REVISE WALL
 SECTION.
  
 13.)PER FBC 1814.3.3, DAMPPROOFING
 IS REQUIRED FOR CONCRETE SLABS.PLEASE
 REVISE THE WALL SECTION (TYPICAL
 CONCRETE SLAB) ON SHEET A8.
  
 14.)EXISTING BEDROOM WINDOWS ARE
 REQUIRED TO BE EGRESS WINDOWS (FBC1005.4
 AND FBC 3401.7.1.2).PLEASE GIVE
 BEDROOM WINDOW INFORMATION; DIMENSIONS,
 TYPE, AND DISTANCE FROM FLOOR.
  
 15.)ON WALL SECTIONS AND DETAILS,
 TWO COURSES OF LINTEL BLOCK W/STEEL IS
 DESCRIBED BUT ONLY ONE IS SHOWN.PLEASE
 REVISE IN ALL SECTIONS TO MAKE THE TEXT
 MATCH THE GRAPHIC.
  
 16.)ATTIC ACCESS IS REQUIRED IN THE
 CABANA.GIVE SIZE AND LOCATION.
  
 17.)ATTIC ACCESS IS REQUIRED IN THE
 ADDITION.GIVE SIZE AND LOCATION.
  
 18.)ATTIC ACCESS REQUIRES INSULATION.
 ALSO, THE DETAIL TEXT REFERS TO A LADDER
 BUT IS NOT SHOWN.PLEASE REVISE THE
 DETAIL.
  
 19.)IF THE FIREPLACE IS NOT FACTORY-
 BUILT, PLEASE PROVIDE A DETAIL.IF IT
 IS FACTORY BUILT, PLEASE COMPLY WITH
 NOTES 20 THROUGH 24.
  
 20.) 2804.4.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND
 MANUFACTURER'S INSTRUCTION.
  
 21.) 2804.4.4. FACTORY-BUILT CHIMNEYS
 FOR USE WITH CLOSED COMBUSTION WOOD
 BURNING APPLIANCES SHALL COMPLY WITH
 THE TYPE HT REQUIREMENT UL 103.
  
 22.) CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
  
 23.) 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
  
 24.) 2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 25.)PLEASE PROVIDE ADDITIONAL
 INFORMATION IN REGARDS TO THE METHOD
 OF SHORING.
  
 26.)PLEASE PROVIDE INFORMATION IN
 REGARDS TO THE SIDING MATERIAL.
  
 27.) PROVIDE STORM PANEL INFORMATION W/
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 28.)FIRESTOP REQUIRED.PLEASE REVISE
 WALL SECTION DETAILS.
  
 29.)PROVIDE A DETAIL FOR THE BAY
 WINDOW.
  
 30.)PROVIDE STRUCTURAL INFORMATION
 ON THE EXISTING PATIO WALLS.ARE THERE
 EXISTING COLUMNS?PROVIDE STRUCTURAL
 CALCULATIONS AND A DETAIL FOR THE
 PROPOSED PORCH TIE BEAM, INCLUDING
 THE CANTALEVERED SECTION OVER THE BAY
 WINDOW.
  
 31.)FOR FOUNDATION DETAIL 1/A3, GIVE
 ALL DIMENSIONS.
  
 32.)FOR DETAIL 2/A3, GIVE CONNECTION
 INFORMATION AT THE TOP OF THE POST.
  
 33.)PROVIDE ADDITIONAL INFORMATION IN
 REGARDS TO UPLIFT AND CALCULATED LOADS.
  
 34.)PROVIDE LOADING INFORMATION FOR
 THE TRUSSES.
  
 35.)THE POOL IS TO COMPLY WITH FBC
 424.2.17.1.INDICATE COMPLIANCE ON
 THE PLAN, EITHER AS EXISTING OR
 PROPOSED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG
 561-659-8096, EXTENSION 8340, OR
 561-805-6724