2003-07-01 00:00:00TRUSSES
  
 1) THE TRUSS LAYOUTS AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED BY THE ENGINEER
 OF RECORD FOR THE STRUCTURE. THEY
 SHOULD BE STAMPED AND SIGNED BY THE
 ENGINEER OF RECORD AS HAVING BEEN
 REVIEWED AND APPROVED.
  
 2) DUE TO DISCREPANCIES BETWEEN THE
 TRUSS LAYOUT AND THE ROOF FRAMING PLAN,
 A REVISED ROOF FRAMING PLAN IS REQUIRED
 TO BE SUBMITTED.
  
 3) SEVERAL OF THE TRUSSES HAVE UPLIFT
 VALUES WHICH EXCEED THE VALUES GIVEN ON
 THE ROOF FRAMING PLAN. TRUSSES A1G, A4,
 A5, B1G, B4G, B2, B3, G3G, G2, G1 HAVE
 HIGHER UPLIFT VALUES.
  
 4) TRUSSES A14 AND A15G HAVE CENTER
 BEARING POINTS WITH UPLIFTS THAT REQUIRE
 ANCHORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714