2003-03-12 00:00:00 | ************** UNSAT ************ |
| |
| 1)NOTE: PLEASE SEE 210-52C-1 FOR KITCHEN |
| COUNTERSPACE RECEPT SPACING. |
| |
| 2)NOTE: PLEASE SEE 210-8/ AND LOCAL |
| AMENDMENTS, ALLL RECEPTS W/IN 6' OF ANY |
| SINK TO BE GFI/GFI PROTECTED. (UTILITY |
| ROOM). |
| |
| 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 |
| MISSING SD AT LOWER LEVEL IN THE |
| VICINITY OF STAIRWAY LEADING TO FLOOR |
| ABOVE AND ON EACH LEVEL THERE AFTER. |
| PLEASE ALSO SEE SAME FOR SD`S NOT |
| PERMITTED IN KITCHENS AND MUST BE A MIN |
| OF 3' FROM KITCHEN/BATHS. |
| |
| 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS |
| MISSING PER 210-52 |
| |
| 5)NOTE: PLEASE SEE 210-70 FOR EGRESS LT |
| PLEASE EITHER PROVIDE AUTOMATIC MEANS |
| OF LIGHTING FOR STAIRWAY AT APT, OR |
| 3-WAY SWITCH AT BOTTOM OF STAIRS. |
| |
| 6)NOTE: PLEASE SEE 225-31 FOR MEANS OF |
| DISC AT DETACHED BLDG. PANEL "C" SHOWS |
| MLO. MUST BE MCB OR PROVIDE DISC. |
| |
| 7)NOTE: PLEASE SIZE SERVICE ENT CONDUCT- |
| ORS PER 310-16/310-15. PLEASE NOTE,EVEN |
| W/ FUSES DOWN SIZING SERVICE, STILL SHOW |
| -S A 475A TOTAL.PLANS SHOWS 4/0`S WHICH |
| UNDER 310-15 ARE ONLY RATED FOR 250A'S |
| PLEASE SEE LOAD IS SHOWN AT 282A'S. |
| PLEASE SIZE ACCORDING TO 310-16. |
| |
| 8)NOTE: PLEASE LIST ALL REQ`D BATH |
| CIRCUIT(S) PER 210-52D/210-11-C3 |
| |
| 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| CIRCUITS PER 210-12 |
| |
| 10)NOTE: PLEASE LIST/SHOW THE REQ`D WASH |
| -ER CIRCUIT PER 220-16, 1500VA |
| |
| 11)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| AT MAIN HOUSE TO FOOTER STEEL AS REQ`D |
| IN 250-50. SHOWN AT DETACHED BLDG OK. |
| |
| PLEASE REVIEW AND SUBMIT THE ABOVE |
| INFORMATION FOR REVIEW. IF THERE ARE |
| ANY QUESTIONS, PLEASE CALL. |
| |