Plan Review Notes
Plan Review Notes For Permit 03021563
Permit Number 03021563
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-12 00:00:00************** UNSAT ************
  
 1)NOTE: PLEASE SEE 210-52C-1 FOR KITCHEN
 COUNTERSPACE RECEPT SPACING.
  
 2)NOTE: PLEASE SEE 210-8/ AND LOCAL
 AMENDMENTS, ALLL RECEPTS W/IN 6' OF ANY
 SINK TO BE GFI/GFI PROTECTED. (UTILITY
 ROOM).
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2
 MISSING SD AT LOWER LEVEL IN THE
 VICINITY OF STAIRWAY LEADING TO FLOOR
 ABOVE AND ON EACH LEVEL THERE AFTER.
 PLEASE ALSO SEE SAME FOR SD`S NOT
 PERMITTED IN KITCHENS AND MUST BE A MIN
 OF 3' FROM KITCHEN/BATHS.
  
 4)NOTE: PLEASE SEE A COUPLE OF RECEPTS
 MISSING PER 210-52
  
 5)NOTE: PLEASE SEE 210-70 FOR EGRESS LT
 PLEASE EITHER PROVIDE AUTOMATIC MEANS
 OF LIGHTING FOR STAIRWAY AT APT, OR
 3-WAY SWITCH AT BOTTOM OF STAIRS.
  
 6)NOTE: PLEASE SEE 225-31 FOR MEANS OF
 DISC AT DETACHED BLDG. PANEL "C" SHOWS
 MLO. MUST BE MCB OR PROVIDE DISC.
  
 7)NOTE: PLEASE SIZE SERVICE ENT CONDUCT-
 ORS PER 310-16/310-15. PLEASE NOTE,EVEN
 W/ FUSES DOWN SIZING SERVICE, STILL SHOW
 -S A 475A TOTAL.PLANS SHOWS 4/0`S WHICH
 UNDER 310-15 ARE ONLY RATED FOR 250A'S
 PLEASE SEE LOAD IS SHOWN AT 282A'S.
 PLEASE SIZE ACCORDING TO 310-16.
  
 8)NOTE: PLEASE LIST ALL REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11-C3
  
 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS PER 210-12
  
 10)NOTE: PLEASE LIST/SHOW THE REQ`D WASH
 -ER CIRCUIT PER 220-16, 1500VA
  
 11)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 AT MAIN HOUSE TO FOOTER STEEL AS REQ`D
 IN 250-50. SHOWN AT DETACHED BLDG OK.
  
 PLEASE REVIEW AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW