2003-03-27 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT A SOIL BEARING REPORT FOR THE |
| TWO STORY RESIDENCE AND THE GARAGE/APT. |
| AS REQUIRED BY FBC 1804.2.2. |
| |
| 4)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR ALL EXTERIOR WINDOW AND |
| DOOR OPENINGS. |
| |
| 5) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. IMPACT |
| PROTECTION OR IMPACT RESISTANT GLAZING |
| IS REQUIRED AT ALL EXTERIOR GLAZED |
| OPENINGS. |
| |
| 6) SEPARATE PERMITS WITH ADDITIONAL FEES |
| WILL BE REQUIRED FOR THE POOL, FENCES, |
| ROOFING, ELECTRIC, MECHANICAL, PLUMBING, |
| AND DRIVEWAY. |
| |
| 7) INDICATE ON THE PLANS THAT THE WIRE |
| MESH IN THE SLAB IS TO BE SUPPORTED ON |
| APPROVED MATERIAL AT 3 FEET ON CENTER |
| MAXIMUM. SEE FBC 1909.3. |
| |
| 8)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 9) THE STRUCTURE IS LOCATED IN AN "A5" |
| FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| BE REQUIRED. CITY CODE REQUIRES THE |
| LOWEST FLOOR TO BE ELEVATED TO SIX |
| INCHES ABOVE THE BASE FLOOD ELEVATION. |
| THE LOWEST FLOOR ELEVATION REQUIRED IS A |
| MINIMUM OF 7.5 FT. ABOVE BASE FLOOD |
| ELEVATION. PLEASE INDICATE THIS ON THE |
| PLANS. |
| |
| 10) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| AND UL LISTING INFORMATION FOR THE GAS |
| FIREPLACE AND FLUE PIPE (IF REQUIRED). |
| |
| 11) SPECIFY THE ROOF SHEATHING FASTENING |
| REQUIREMENTS AND ZONES ON THE PLANS. |
| SEE CITY AMENDMENTS TO FBC TABLE 2306.1. |
| NOTE: MEAN ROOF HEIGHT OF 25 FEET |
| REQUIRES 8D RING SHANK NAILS IN ZONE 3. |
| |
| 12) SPECIFY ON THE PLANS THE REQUIRED |
| 1-1/2" BLOCK RECESS IN THE SLAB AT THE |
| EXTERIOR MASONRY WALL. CITY AMENDMENTS |
| TO FBC 2111.1.9. |
| |
| 13) THE WALL TYPE ON A-1.0 LISTS 3/4" |
| STUCCO AND THE WALL SECTION ON A-4.0 |
| SPECIFIES 5/8" STUCCO. PLEASE CORRECT. |
| |
| 14) THE WINDOWS AT THE MASTER BATH TUB |
| ARE REQUIRED TO BE SAFETY GLASS OR |
| IMPACT RESISTANT GLAZING. SEE FBC 2405.2 |
| |
| 15) INDICATE THE LOCATIONS OF THE |
| DRAFTSTOPPING AT THE FLOOR/CEILING |
| ASSEMBLIES FOR THE RESIDENCE AND THE |
| GARAGE/APT. FBC 2305.2.2 |
| |
| 16) THE WALL TYPES ON A-7 LISTS 3/4" |
| STUCCO AND THE WALL SECTION ON A-7 LISTS |
| 5/8" STUCCO. PLEASE CORRECT. |
| |
| 17) SUBMIT COMPLETE STRUCTURAL PLANS FOR |
| THE GARAGE/APARTMENT. INCLUDE FOUNDATION |
| WALL REINFORMENT, LINTELS, FLOOR FRAMING |
| ROOF FRAMING, ROOF FRAMING, STAIRS, |
| BALCONIES, ETC. |
| |
| 18) THE EXTERIOR EXIT STAIRS FOR THE |
| GARAGE/APARTMENT DOES NOT COMPLY WITH |
| FBC REQUIREMENTS. THE DOOR MUST OPEN TO |
| A ROOFED OVER BALCONY, PORCH OR GALLERY |
| NOT LESS THAN 4-1/2 FEET WIDE AND MUST |
| BE LOCATED AT LEAST 10 FEET FROM |
| ADJACENT PROPERTY LINES. THE STAIRS |
| SHALL BE SEPARATED FROM THE INTERIOR OF |
| THE BUILDING BY WALLS WITH A FIRE |
| RESISTANCE RATING OF ONE HOUR WITH FIXED |
| OR SELF-CLOSING OPENING PROTECTIVES AS |
| REQUIRED FOR ENCLOSED STAIRS. SEE FBC |
| 1006.2, 1006.2.2, 1006.2.4 |
| |
| 19) SPECIFY THE REQUIRED SPACING OF |
| INTERMEDIATE AND BOTTOM RAILS FOR THE |
| GUARDRAILS AT THE GARAGE/APARTMENT. |
| |
| 20) THE TIE BEAM AT THE COVERED PORCH ON |
| THE FOUNDATION PLAN ON SHEET 1 ARE |
| LABELED B1 AND THE TIEBEAM SCHEDULE |
| LISTS TB-1. PLEASE COORDINATE. |
| |
| 21) THE LOCATIONS OF THE 6X6 POST ON |
| STRUCTURAL SHEETS 2 & 3 DO NOT MATCH THE |
| ARCHITECTURAL DRAWINGS FOR THE SECOND |
| FLOOR COVERED BALCONY. |
| |
| 22) REVIEW THE CONNECTORS FOR THE 6X6 |
| POSTS AT THE COVERED BALCONY. (HU 212-3 |
| 1810# UPLIFT VALUE AND EPB 66 WITH 1500# |
| UPLIFT VALUE) THE UPLIFTS GIVEN FOR THE |
| TRUSSES APPEAR TO EXCEED THESE LIMITS. |
| |
| 23) SPECIFY THE CONNECTORS USED TO |
| ATTACH THE 3-2X12 HEADERS AT THE COVERED |
| BALCONY TO THE MASONRY WALLS OF THE |
| STRUCTURE. |
| |
| 24) THE 2 SIMPSON HETAL 20 CONNECTORS |
| SPECIFIED ON SHEET 3 HAVE AN UPLIFT |
| RATING OF 2035# AND THE UPLIFT REQUIRED |
| AT THE HIP GIRDERS IS 2853# AND 2291#. |
| PLEASE CORRECT. |
| |
| 25) SPECIFY ALL REQUIRED CONNECTORS AND |
| PROVIDE AN ANCHOR SCHEDULE FOR RESIDENCE |
| AND GARAGE /APT. |
| |
| 26) PROVIDE STRUCTURAL DETAILS OF WHAT |
| APPEARS TO BE A CONCRETE DECK EXTENSION |
| (EYEBROW) AT THE COVERED BALCONY ON THE |
| SECOND FLOOR. SEE WALL SECTION 1 ON A4.1 |
| |
| 27) PROVIDE DETAIL OF WATER PROOFING AT |
| BALCONY FLOORS. |
| |
| 28) SPECIFY THE CONNECTIONS OF THE FLOOR |
| TRUSSES TO THE DOUBLE 2 X 10 LEDGERS. |
| INDICATE THE CONNECTORS AND FASTENERS. |
| |
| 29) PROVIDE DETAILS OF THE CONNECTIONS |
| OF THE 2 X 10 FLOOR JOISTS TO THE |
| LEDGERS AT THE SECOND FLOOR BALCONIES. |
| INDICATE THE CONNECTORS AND FASTENERS |
| FOR THE JOIST TO LEDGER CONNECTIONS AND |
| THE FASTENERS AND SPACING FOR THE LEDGER |
| TO MASONRY OR CONCRETE BEAM CONNECTIONS. |
| |
| 30) SPECIFY THE SIZE OF THE FLOOR JOISTS |
| AT THE COVERED BALCONY. |
| |
| 31) INDICATE THE MATERIALS THAT WILL BE |
| USED TO CLAD THE EXTERIOR CEILINGS AT |
| THE COVERED PORCHES AND BALCONIES. |
| |
| 32) THE SECOND FLOOR FRAMING PLAN SHOWS |
| JOISTS CANTILEVERED OVER WOOD BEAMS, |
| WHICH IS INCONSISTANT WITH THE |
| ARCHITECTURAL PLANS. PLEASE REVISE. |
| |
| 33) SEE ADDITIONAL NOTES ON ONE SET OF |
| THE PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |