Plan Review Notes
Plan Review Notes For Permit 03021563
Permit Number 03021563
Review Stop B
Sequence Number 1
Notes
Date Text
2003-03-27 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BEARING REPORT FOR THE
 TWO STORY RESIDENCE AND THE GARAGE/APT.
 AS REQUIRED BY FBC 1804.2.2.
  
 4)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR ALL EXTERIOR WINDOW AND
 DOOR OPENINGS.
  
 5) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. IMPACT
 PROTECTION OR IMPACT RESISTANT GLAZING
 IS REQUIRED AT ALL EXTERIOR GLAZED
 OPENINGS.
  
 6) SEPARATE PERMITS WITH ADDITIONAL FEES
 WILL BE REQUIRED FOR THE POOL, FENCES,
 ROOFING, ELECTRIC, MECHANICAL, PLUMBING,
 AND DRIVEWAY.
  
 7) INDICATE ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB IS TO BE SUPPORTED ON
 APPROVED MATERIAL AT 3 FEET ON CENTER
 MAXIMUM. SEE FBC 1909.3.
  
 8)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 9) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED. CITY CODE REQUIRES THE
 LOWEST FLOOR TO BE ELEVATED TO SIX
 INCHES ABOVE THE BASE FLOOD ELEVATION.
 THE LOWEST FLOOR ELEVATION REQUIRED IS A
 MINIMUM OF 7.5 FT. ABOVE BASE FLOOD
 ELEVATION. PLEASE INDICATE THIS ON THE
 PLANS.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING INFORMATION FOR THE GAS
 FIREPLACE AND FLUE PIPE (IF REQUIRED).
  
 11) SPECIFY THE ROOF SHEATHING FASTENING
 REQUIREMENTS AND ZONES ON THE PLANS.
 SEE CITY AMENDMENTS TO FBC TABLE 2306.1.
 NOTE: MEAN ROOF HEIGHT OF 25 FEET
 REQUIRES 8D RING SHANK NAILS IN ZONE 3.
  
 12) SPECIFY ON THE PLANS THE REQUIRED
 1-1/2" BLOCK RECESS IN THE SLAB AT THE
 EXTERIOR MASONRY WALL. CITY AMENDMENTS
 TO FBC 2111.1.9.
  
 13) THE WALL TYPE ON A-1.0 LISTS 3/4"
 STUCCO AND THE WALL SECTION ON A-4.0
 SPECIFIES 5/8" STUCCO. PLEASE CORRECT.
  
 14) THE WINDOWS AT THE MASTER BATH TUB
 ARE REQUIRED TO BE SAFETY GLASS OR
 IMPACT RESISTANT GLAZING. SEE FBC 2405.2
  
 15) INDICATE THE LOCATIONS OF THE
 DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLIES FOR THE RESIDENCE AND THE
 GARAGE/APT. FBC 2305.2.2
  
 16) THE WALL TYPES ON A-7 LISTS 3/4"
 STUCCO AND THE WALL SECTION ON A-7 LISTS
 5/8" STUCCO. PLEASE CORRECT.
  
 17) SUBMIT COMPLETE STRUCTURAL PLANS FOR
 THE GARAGE/APARTMENT. INCLUDE FOUNDATION
 WALL REINFORMENT, LINTELS, FLOOR FRAMING
 ROOF FRAMING, ROOF FRAMING, STAIRS,
 BALCONIES, ETC.
  
 18) THE EXTERIOR EXIT STAIRS FOR THE
 GARAGE/APARTMENT DOES NOT COMPLY WITH
 FBC REQUIREMENTS. THE DOOR MUST OPEN TO
 A ROOFED OVER BALCONY, PORCH OR GALLERY
 NOT LESS THAN 4-1/2 FEET WIDE AND MUST
 BE LOCATED AT LEAST 10 FEET FROM
 ADJACENT PROPERTY LINES. THE STAIRS
 SHALL BE SEPARATED FROM THE INTERIOR OF
 THE BUILDING BY WALLS WITH A FIRE
 RESISTANCE RATING OF ONE HOUR WITH FIXED
 OR SELF-CLOSING OPENING PROTECTIVES AS
 REQUIRED FOR ENCLOSED STAIRS. SEE FBC
 1006.2, 1006.2.2, 1006.2.4
  
 19) SPECIFY THE REQUIRED SPACING OF
 INTERMEDIATE AND BOTTOM RAILS FOR THE
 GUARDRAILS AT THE GARAGE/APARTMENT.
  
 20) THE TIE BEAM AT THE COVERED PORCH ON
 THE FOUNDATION PLAN ON SHEET 1 ARE
 LABELED B1 AND THE TIEBEAM SCHEDULE
 LISTS TB-1. PLEASE COORDINATE.
  
 21) THE LOCATIONS OF THE 6X6 POST ON
 STRUCTURAL SHEETS 2 & 3 DO NOT MATCH THE
 ARCHITECTURAL DRAWINGS FOR THE SECOND
 FLOOR COVERED BALCONY.
  
 22) REVIEW THE CONNECTORS FOR THE 6X6
 POSTS AT THE COVERED BALCONY. (HU 212-3
 1810# UPLIFT VALUE AND EPB 66 WITH 1500#
 UPLIFT VALUE) THE UPLIFTS GIVEN FOR THE
 TRUSSES APPEAR TO EXCEED THESE LIMITS.
  
 23) SPECIFY THE CONNECTORS USED TO
 ATTACH THE 3-2X12 HEADERS AT THE COVERED
 BALCONY TO THE MASONRY WALLS OF THE
 STRUCTURE.
  
 24) THE 2 SIMPSON HETAL 20 CONNECTORS
 SPECIFIED ON SHEET 3 HAVE AN UPLIFT
 RATING OF 2035# AND THE UPLIFT REQUIRED
 AT THE HIP GIRDERS IS 2853# AND 2291#.
 PLEASE CORRECT.
  
 25) SPECIFY ALL REQUIRED CONNECTORS AND
 PROVIDE AN ANCHOR SCHEDULE FOR RESIDENCE
 AND GARAGE /APT.
  
 26) PROVIDE STRUCTURAL DETAILS OF WHAT
 APPEARS TO BE A CONCRETE DECK EXTENSION
 (EYEBROW) AT THE COVERED BALCONY ON THE
 SECOND FLOOR. SEE WALL SECTION 1 ON A4.1
  
 27) PROVIDE DETAIL OF WATER PROOFING AT
 BALCONY FLOORS.
  
 28) SPECIFY THE CONNECTIONS OF THE FLOOR
 TRUSSES TO THE DOUBLE 2 X 10 LEDGERS.
 INDICATE THE CONNECTORS AND FASTENERS.
  
 29) PROVIDE DETAILS OF THE CONNECTIONS
 OF THE 2 X 10 FLOOR JOISTS TO THE
 LEDGERS AT THE SECOND FLOOR BALCONIES.
 INDICATE THE CONNECTORS AND FASTENERS
 FOR THE JOIST TO LEDGER CONNECTIONS AND
 THE FASTENERS AND SPACING FOR THE LEDGER
 TO MASONRY OR CONCRETE BEAM CONNECTIONS.
  
 30) SPECIFY THE SIZE OF THE FLOOR JOISTS
 AT THE COVERED BALCONY.
  
 31) INDICATE THE MATERIALS THAT WILL BE
 USED TO CLAD THE EXTERIOR CEILINGS AT
 THE COVERED PORCHES AND BALCONIES.
  
 32) THE SECOND FLOOR FRAMING PLAN SHOWS
 JOISTS CANTILEVERED OVER WOOD BEAMS,
 WHICH IS INCONSISTANT WITH THE
 ARCHITECTURAL PLANS. PLEASE REVISE.
  
 33) SEE ADDITIONAL NOTES ON ONE SET OF
 THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202