Plan Review Notes For Permit 03021543 |
Permit Number |
03021543 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-06-11 00:00:00 | ************* UNSAT ************* | | | | 1)NOTE: PLEASE SEE NOTE FROM FIRST | | REVIEW. PLEASE SHOW ALL CIRCUITING | | INCLUDING EM/EXT LTS. PLEASE SEE 700-12E | | FOR CIRCUITING OF EM/EXT LTS. | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | AS ON PREVIOUS NOTES. 220-3,220-10,220-1 | | 1, ETC. PLEASE SHOW ALL CONTINUOUS | | LOADS AT 125%. 215-3/230-42 | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | GROUNDING CONDUCTOR FROM MAIN DISC TO | | PANEL AND SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL.. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|