Plan Review Notes For Permit 03021510 |
Permit Number |
03021510 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-15 00:00:00 | SHOP DRAWINGS FOR GUARDRAIL | | | | ******CORRECTIONS******* | | | | 1.)THE PLAN SHOWS A LANDING OF 5'. | | GUARDRAIL ONE DOES NOT SHOW THIS | | LANDING.CLEARLY SHOW ON THE SHOP | | DRAWINGS OF THE GUARDRAIL THE MIN. 60" | | REQUIRED FOR LANDINGS FBX11-4.8.4. | | | | 2.)THE ORIGINAL PLAN SHOWS A 1'6" | | EXTENSION OF THE GUARDRAIL (ONE) AT THE | | TOP AND BOTTOM OF THE GUARDRAIL.THE | | SHOP DRAWINGS HAVE REDUCED THIS TO | | 1'4" AND 1'5 1/2".A MINIMUM OF 18" | | IS REQUIRED FBC11-4.8.5(2). | | | | 3.)THE DIMENSION FOR HANDICAP RAMP | | TWO WAS REVISED TO BE 34" (FROM 32"), | | BUT THE DIMENSIONS ON THE OTHER SIDE OF | | THE DETAIL (20" AND 1') WERE NOT | | CHANGED. | | | | 4.)THE ORIGINAL PLAN BY LCA | | ARCHITECTURE, INC. STATES ON SHEET A3: | | "RAIL NOTE:CONTRACTOR SHALL PROVIDE | | RAIL ENGINEERING & SHOP DRAWINGS FOR | | APPROVAL."HAVE THE ARCHITECT REVIEW | | THE SHOP DRAWINGS. | | | | 5.)THE RAILING IS TO COMPLY WITH | | FBC1608.2. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|