Plan Review Notes For Permit 03021472 |
Permit Number |
03021472 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-12 00:00:00 | ************** UNSAT ***************** | | | | 1)NOTE: PLEASE SEE MISSING SD IN ROOM | | AT FRONT DOOR W/ CLOSET. NFPA-72 8-1.4.2 | | | | 2)NOTE: PLEASE SEE MISSING EGRESS LIGHT- | | ING AND CONTROL AT BACK DOOR. 210-70 | | | | 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI | | PROTECTED.210-8-A-6 | | | | 4)NOTE: PLEASE SEE MISSING SOME RECEPTS | | FOR KITCHEN COUNTERSPACE. 210-52-C1 | | | | 5)NOTE: PLEASE SEE MISSING HALL RECEPT | | 210-52H | | | | 6)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | TWO CIRCUITS FOR SM APPL AND SHOWS LOAD | | FOR THREE? PLEASE CORRELATE. | | | | 7)NOTE: PLEASE CORRELATE SUB PANEL | | WITH MLO SHOWNAT 65A'S, MAIN PANEL | | SHOWS AT 60A. | | | | 8)NOTE: PLEASE SHOW ROOM DESIGNATIONS | | ON FLOOR LAYOUT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|