Plan Review Notes For Permit 03021468 |
Permit Number |
03021468 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-10 00:00:00 | ********** NOTES REDLINED.********* | | | | PANEL SCHEDULE AND RISER DIAGRAM TO | | CORRELATE. PANEL SHOWS 2P-40/#10 FOR | | 60A SUB PANEL. |
|