Notes |
Date |
Text |
2003-03-07 00:00:00 | ************** UNSAT ***************** | | | | 1)NOTE: PLEASE CORRELATE OCP/KW/AWG FOR | | AHU #2. | | | | 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR | | MAIN PANEL SHOWING LOADS. | | | | 3)NOTE: PLEASE SEE LOAD CALCULATIONS, | | SHOWS 4 SM APPL AND WASHER E@ 1500 AND | | + TO 6KW. PLEASE RE-CONFIGURE. SHOULD BE | | 7.5KW. | | | | 4)NOTE: PLEASE ALSO CORRELATE PANEL | | SCHEDULE AND LOAD CALCS, SHOWS 4 SM APPL | | ON LOAD CALCS, AND ONLY 2 SHOWN ON PANEL | | SCHEDULE. | | | | 5)NOTE: PLEASE SEE MISSING RECEPT IN | | BEDROOM #4. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|