Plan Review Notes
Plan Review Notes For Permit 03021123
Permit Number 03021123
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-07 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE OCP/KW/AWG FOR
 AHU #2.
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE FOR
 MAIN PANEL SHOWING LOADS.
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS 4 SM APPL AND WASHER E@ 1500 AND
 + TO 6KW. PLEASE RE-CONFIGURE. SHOULD BE
 7.5KW.
  
 4)NOTE: PLEASE ALSO CORRELATE PANEL
 SCHEDULE AND LOAD CALCS, SHOWS 4 SM APPL
 ON LOAD CALCS, AND ONLY 2 SHOWN ON PANEL
 SCHEDULE.
  
 5)NOTE: PLEASE SEE MISSING RECEPT IN
 BEDROOM #4.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372