2003-03-10 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SPECIFY ON THE PLANS THAT WIRE MESH |
| IN THE SLAB IS TO BE SUPPORTED AT A MAX. |
| OF 3 FT OC AS REQUIRED BY FBC 1909.3. |
| |
| 3) GLAZING WITHIN 3 FEET HORIZONTALLY OF |
| A TUB OR SHOWER IS REQUIRED TO BE |
| TEMPERED. THIS IS NOT CLEARLY INDICATED |
| BY NOTE #9 ON SHEET 1. PLEASE CLARIFY. |
| |
| 4) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| ON THE PLANS. FBC 2309.6 |
| |
| 5) SPECIFY THE LENGTH/EMBED DEPTH OF |
| 5/8" EXPANSION BOLTS FOR THE GARAGE DOOR |
| BUCKS ON SHEET 4. |
| |
| 6) THE REAR GABLE END ADJACENT TO THE |
| VAULTED CEILING IS REQUIRED TO BE |
| CONTINOUS FROM THE FLOOR TO THE CEILING |
| DIAPHRAGM PER FBC 1918.3.2. PLEASE |
| PROVIDE A DETAIL OF THE RAKE BEAM AT |
| THIS LOCATION. |
| |
| 7) THE SITE SPECIFIC ENGINEERING FOR THE |
| NORANDEX PRODUCTS ARE REQUIRED TO HAVE |
| THE EMBOSSED SEAL OF THE DESIGNER OF |
| RECORD FOR THE STRUCTURE AND THE JOB |
| LOCATION LISTED ON THE THE FORM. THIS IS |
| REQUIRED BY THE BUILDING OFFICIAL PER |
| FBC 103.7. |
| |
| 8) THE INFORMATION LISTED ON THE ENERGY |
| CALCULATION FORM IS INCORRECT. THE R- |
| VALUES FOR THE EXTERIOR AND ADJACENT |
| WALLS ARE REVERSED. SUBMITTED CORRECTED |
| FORM. |
| |
| 9) PROVIDE THE MANUFACTURER'S |
| SPECIFICATIONS AND ANDUL LISTING |
| INFORMATION FOR THE ONE HOUR FIRE RATED |
| GLASS BLOCK ASSEMBLY. |
| |
| 10) SOME OF THE OPENING SIZES ON THE |
| STORM PANEL SCHEDULE DO NOT CORRESPOND |
| WITH TOSE ON THE WINDOW SCHEDULE ON |
| SHEET 2 OF THE PLANS. PLEASE REVISE. |
| |
| 11) PROVIDE PRODUCT APPROVALS FOR THE |
| HORIZONTAL SLIDING WINDOW WITH THE XOX |
| CONFIGURATION AS SHOWN ON THE PLANS. |
| |
| 12) THE LOMR INFORMATION LISTED ON THE |
| SURVEY IS INCORRECT. PLEASE REVISE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |