Plan Review Notes For Permit 03021059
Permit Number 03021059
Review Stop B
Sequence Number 1
Notes
Date Text
2003-03-10 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY ON THE PLANS THAT THE WWM IN
 THE SLAB IS TO BE SUPPORTED ON APPROVED
 MATERIALS AT 3 FT O.C. MAX. FBC 1909.3
  
 3) THE WINDOW IN BATH #2 IS REQUIRED TO
 HAVE SAFETY GLAZING BECAUSE IT IS WITHIN
 3 FT HORIZONTALLY OF THE TUB/SHOWER.
 THIS IS NOT CLEARLY INDICATED BY GENERAL
 NOTE #9 ON SHEET 1. PLEASE REVISE.
  
 4) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE PLANS.
  
 5) PROVIDE A DETAIL OF THE RAKE BEAM AT
 THE REAR GABLE END THAT IS ADJACENT TO
 THE VAULTED CEILING.
  
 6) THE EMBOSSED SEAL OF THE DESIGNER OF
 RECORD AND THE LOCATION OF THE JOB IS
 REQUIRED ON THE NORANDEX SITE SPECIFIC
 PRODUCT APPROVAL.
  
 7) THE INFORMATION LISTED ON THE ENERGY
 CALCULATION FORM IS INCORRECT FOR THE
 R-VALUES OF THE EXTERIOR AND ADJACENT
 WALLS. PLEASE CORRECT.
  
 8) PROVIDE THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK ASSEMBLY.
  
 9) SOME OF THE OPENING SIZES LISTED IN
 THE STORM PANEL SCHEDULE DO NOT
 CORRESPOND WITH THE WINDOW SCHEDULE ON
 THE PLANS. PLEASE REVISE.
  
 10) PROVIDE PRODUCT APPROVALS FOR A
 HORIZONTAL SLIDING WINDOW WITH AN XOX
 CONFIGURATION AS SHOWN ON THE PLANS.
  
 11) THE LOMR INFORMATION ON THE SURVEY
 IS INCORRECT. PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202