2003-03-10 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SPECIFY ON THE PLANS THAT THE WWM IN |
| THE SLAB IS TO BE SUPPORTED ON APPROVED |
| MATERIALS AT 3 FT O.C. MAX. FBC 1909.3 |
| |
| 3) THE WINDOW IN BATH #2 IS REQUIRED TO |
| HAVE SAFETY GLAZING BECAUSE IT IS WITHIN |
| 3 FT HORIZONTALLY OF THE TUB/SHOWER. |
| THIS IS NOT CLEARLY INDICATED BY GENERAL |
| NOTE #9 ON SHEET 1. PLEASE REVISE. |
| |
| 4) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| ON THE PLANS. |
| |
| 5) PROVIDE A DETAIL OF THE RAKE BEAM AT |
| THE REAR GABLE END THAT IS ADJACENT TO |
| THE VAULTED CEILING. |
| |
| 6) THE EMBOSSED SEAL OF THE DESIGNER OF |
| RECORD AND THE LOCATION OF THE JOB IS |
| REQUIRED ON THE NORANDEX SITE SPECIFIC |
| PRODUCT APPROVAL. |
| |
| 7) THE INFORMATION LISTED ON THE ENERGY |
| CALCULATION FORM IS INCORRECT FOR THE |
| R-VALUES OF THE EXTERIOR AND ADJACENT |
| WALLS. PLEASE CORRECT. |
| |
| 8) PROVIDE THE MANUFACTURER'S SPECS. AND |
| LISTING INFORMATION FOR THE ONE HOUR |
| FIRE RATED GLASS BLOCK ASSEMBLY. |
| |
| 9) SOME OF THE OPENING SIZES LISTED IN |
| THE STORM PANEL SCHEDULE DO NOT |
| CORRESPOND WITH THE WINDOW SCHEDULE ON |
| THE PLANS. PLEASE REVISE. |
| |
| 10) PROVIDE PRODUCT APPROVALS FOR A |
| HORIZONTAL SLIDING WINDOW WITH AN XOX |
| CONFIGURATION AS SHOWN ON THE PLANS. |
| |
| 11) THE LOMR INFORMATION ON THE SURVEY |
| IS INCORRECT. PLEASE REVISE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |