2003-02-21 00:00:00 | 1) NO EMERGENCY LIGHTS OR EXIT SIGNS | | SHOWN ON THE PLANS. | | | | 2) NO INFORMATION PROVIDED CONCERNING | | FIRE EXTINGUISHERS. | | | | 3) PLEASE INDICATE SIZES OF EXISTING | | DOORS. | | | | 4) HOW MANY EMPLOYEE'S WILL BE WORKING | | IN THE TENANT SPACE. | | | | 5) TEN INCH TREADS SHOWN ON STAIR. A | | MINIMUM OF AT LEAST ELEVEN INCH TREADS | | ARE REQUIRED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|