Plan Review Notes For Permit 03021019 |
Permit Number |
03021019 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-21 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SHOW/CLARIFY WHAT TYPE | | OF SANDING OR MATERIALS UNDER ART 500 | | NEC. | | | | 2)NOTE: PLEASE SHOW ANY EXIST OR NEW | | REQ`D EXIT AND/OR EM LTS, PLEASE ALSO | | SEE 700-12E FOR CIRCUITING. | | | | 3)NOTE: TWO SPACE ARE SHOWN ON PANEL | | SCHEDULE W/ 2P 50A BRKRS? SPACES ARE | | BLANK, PLEASE CLARIFY. | | | | 4)NOTE: PLEASE SEE 600-5 FOR REQ`D | | SIGN CIRCUIT. | | | | 5)NOTE: PLEASE SHOW LOAD CALCULATION OF | | EXSITING AND NEW PER 220-3,220-10,220-11 | | 220-13 AND PLEASE SHOW ALL CONTINUOUS | | LOADS AT 125%. 230-42 215-3 ECT. | | | | PLEASE SEE ANY COMMENTS FROM OTHER | | REVIEWERS THAT MAY AFFECT ELECTRICAL | | PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|