Plan Review Notes
Plan Review Notes For Permit 03021019
Permit Number 03021019
Review Stop E
Sequence Number 1
Notes
Date Text
2003-02-21 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW/CLARIFY WHAT TYPE
 OF SANDING OR MATERIALS UNDER ART 500
 NEC.
  
 2)NOTE: PLEASE SHOW ANY EXIST OR NEW
 REQ`D EXIT AND/OR EM LTS, PLEASE ALSO
 SEE 700-12E FOR CIRCUITING.
  
 3)NOTE: TWO SPACE ARE SHOWN ON PANEL
 SCHEDULE W/ 2P 50A BRKRS? SPACES ARE
 BLANK, PLEASE CLARIFY.
  
 4)NOTE: PLEASE SEE 600-5 FOR REQ`D
 SIGN CIRCUIT.
  
 5)NOTE: PLEASE SHOW LOAD CALCULATION OF
 EXSITING AND NEW PER 220-3,220-10,220-11
 220-13 AND PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%. 230-42 215-3 ECT.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372