Date |
Text |
2004-09-21 00:00:00 | ******** UNSAT *********** |
| |
| PLEASE SEE REVISIONS FOR SHEETS : |
| E-1,5,8,E-8A-CU, E-9A-CU, E9-10. |
| |
| PLEASE SEE COMMENTS/REDLINESFROM PREV- |
| -IOUS REVIEWS. |
| |
| 1)NOTE: PLEASE SEE "DETAIL #2" FOR |
| COOKING EQUIPMENT. THIS SHOWS BOTH UNITS |
| BEING CONNECTED TO A "J-BOX" WITH NO |
| DISCONNECTING MEANS. PLEASE SEE SOME |
| UNITS PANEL IS W/IN SITE, YET SOME ARE |
| NOT. PLEASE SEE 422.30,31,33 ETC FOR |
| REQUIRED MEANS OF DICONNECT. |
| |
| 2)NOTE: PLEASE ALSO SEE SAME "DETAIL #2" |
| WHICH DOES NOT INDICATE ANY NEUTRAL |
| CONDUCTOR AS REQUIRED UNDER 250.140. |
| |
| 3)NOTE: PLEASE SEE REVISION FOR RFI-323, |
| WHICH HAS INCLUDED LTS AND SD'S ON ARC- |
| -FAULT PROTECTED BRKRS.THIS IS OK, HOW- |
| -EVER, NOTE FOR ARC FAULT PROTECTION |
| "**" ONLY INDICATES RECEPTS. THIS APPEAR |
| -S TO JUST BE A NOTE THAT HAS NOT BEEN |
| REVISED YET? |
| |
| 4)NOTE: PLEASE SEE RESPONSE LETTER FROM |
| FES DATED AUGUST 20, 2004 FROM MARVIN |
| SANCHEZ. NOTE(RESPONSE) # 4 MENTIONS BLD |
| DEPARTMENT COMMENTS: DINING RM RECEPTS |
| HAS BEEN CHANGED TO ARC FAULT PROTECTION |
| ??? PLEASE VERIFY COMMENT AND/OR WHERE/ |
| WHY THIS CHANGE WAS MADE. DINING RM |
| RECEPTS ARE NOT REQUIRED TO BE ARC FAULT |
| PROTECTED, UNLESS SO DESIRED. |
| |
| PLEASE SEE OTHER COMMENTS FROM OTHER |
| REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |