Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop B1
Sequence Number 77
Notes
Date Text
2005-04-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/1/05 FOR SECTION
 THROUGH DEMISING WALL IN C-3 UNIT
 KITCHEN
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 701.2FIRE RESISTANCE.THE
 PROPOSED WALL TYPE SHALL BE SHOWN TO
 HAVE PERFORMED SATISFACTORILY WHEN
 TESTED TO THE REQUIREMENTS OF ASTM E 119
 IT IS NOTED THAT THE SUBMITTED SHEETS
 MAKE REFERENCE TO TEST NUMBER U OF C
 7-31-62(UNIVERSITY OF CALIFORNIA).
 SUBMIT A COPY OF THE TEST REPORT OR
 OTHER DOCUMENTATION TO SHOW COMPLIANCE
 WITH ASTM E 119.
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  