Plan Review Notes For Permit 03020961 |
Permit Number |
03020961 |
|
Review Stop |
FIRE |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2004-07-30 00:00:00 | 1) TWO FIRE DEPARTMENT CONNECTIONS ARE | | REQUIRED. TWO 2 1/2 INCH CONNECTIONS | | ARE REQUIRED AT BOTH LOCATIONS. | | | | 2) ARE THE PRESSURE REGULATING | | DEVICES PLANNED FOR USE SET IN THE | | FIELD OR THE FACTORY. PLEASE ADVISE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|