2005-02-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FLAT ROOFING PRODUCT APPROVAL REVISION
 SUBMITTED ON 1/20/05 FOR ELEVATOR
 MACHINE ROOM ROOF.
  
 FROM THE WIND LOAD PRESSURE SUMMARY
 SHEETS S-22 AND S-23, THE DESIGN WIND
 NEGATIVE PRESSURE ON THE THE ELEVATOR
 MACHINE ROOM ROOF IS UP TO -100 PSF.
 THE SUBMITTED GAF PRODUCT APPROVAL NOA#
 04-0611.01 COVERS SYSTEMS WITH MAXIMUM
 DESIGN PRESSURES RANGING FROM -52.5 PSF
 TO -242.5 PSF.WHICH SYSTEM IS
 PROPOSED?
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH SYSTEM IS TO BE USED.