Plan Review Notes For Permit 03020961 |
Permit Number |
03020961 |
|
Review Stop |
B1 |
Sequence Number |
60 |
|
Notes |
Date |
Text |
2005-02-04 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6716 | | E-MAIL: [email protected] | | | | FLAT ROOFING PRODUCT APPROVAL REVISION | | SUBMITTED ON 1/20/05 FOR ELEVATOR | | MACHINE ROOM ROOF. | | | | FROM THE WIND LOAD PRESSURE SUMMARY | | SHEETS S-22 AND S-23, THE DESIGN WIND | | NEGATIVE PRESSURE ON THE THE ELEVATOR | | MACHINE ROOM ROOF IS UP TO -100 PSF. | | THE SUBMITTED GAF PRODUCT APPROVAL NOA# | | 04-0611.01 COVERS SYSTEMS WITH MAXIMUM | | DESIGN PRESSURES RANGING FROM -52.5 PSF | | TO -242.5 PSF.WHICH SYSTEM IS | | PROPOSED? | | THE PRODUCT APPROVAL SHEETS SHALL BE | | MARKED, AS APPROPRIATE, TO IDENTIFY | | WHICH SYSTEM IS TO BE USED. |
|