2004-12-14 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| ALTERNATIVE PRODUCT APPROVAL SUBMITTED |
| ON 12/14/04 FOR DOOR S1-2A, FIRST FLOOR |
| STAIR 2 EXIT DISCHARGE DOOR TO |
| EXTERIOR. |
| |
| 1) THE PRODUCT APPROVAL WAS BROUGHT IN |
| AS A SUBMITTAL FOR ZERO FEE.IT IS IN |
| FACT A REVISION AND A REVISION FEE OF |
| $60 IS DUE. |
| |
| 2) FBC 1606.1WIND PRESSURES ON DOOR |
| S1-2A.SHEET S-22, WIND TUNNEL |
| ANALYSIS |
| RESULTS, SHOWS A PEAK NEGATIVE PRESSURE |
| OF -80 PSF, FOR THIS LOCATION ON THE |
| BUILDING.THIS EXCEEDS THE -70 PSF |
| DESIGN PRESSURE RATING GIVEN IN THE |
| SUBMITTED INGERSOLL-RAND COMMERCIAL |
| STEEL DOOR PRODUCT APPROVAL NOA# |
| 02-712.01 AND IS THUS OUTSIDE THE SCOPE |
| OF THE PRODUCT APPROVAL.THIS DOOR HAS |
| NOT BEEN DEMONSTRATED AS SUITABLE FOR |
| USE IN THIS LOCATION. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |