2004-12-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 ALTERNATIVE PRODUCT APPROVAL SUBMITTED
 ON 12/14/04 FOR DOOR S1-2A, FIRST FLOOR
 STAIR 2 EXIT DISCHARGE DOOR TO
 EXTERIOR.
  
 1) THE PRODUCT APPROVAL WAS BROUGHT IN
 AS A SUBMITTAL FOR ZERO FEE.IT IS IN
 FACT A REVISION AND A REVISION FEE OF
 $60 IS DUE.
  
 2) FBC 1606.1WIND PRESSURES ON DOOR
 S1-2A.SHEET S-22, WIND TUNNEL
 ANALYSIS
 RESULTS, SHOWS A PEAK NEGATIVE PRESSURE
 OF -80 PSF, FOR THIS LOCATION ON THE
 BUILDING.THIS EXCEEDS THE -70 PSF
 DESIGN PRESSURE RATING GIVEN IN THE
 SUBMITTED INGERSOLL-RAND COMMERCIAL
 STEEL DOOR PRODUCT APPROVAL NOA#
 02-712.01 AND IS THUS OUTSIDE THE SCOPE
 OF THE PRODUCT APPROVAL.THIS DOOR HAS
 NOT BEEN DEMONSTRATED AS SUITABLE FOR
 USE IN THIS LOCATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS