Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop P
Sequence Number 4
Notes
Date Text
2004-06-02 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-8 BOILER ROOM, 1-1/4" RVD SHALL
 NOT DRAIN INTO THE FLOOR DRAIN. FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE.
 EITHER A FLOOR SINK OR A HUB DRAIN SHALL
 BE APPROVED FOR INDIRECT WASTE PER SEC.
 802.3 OR 802.3.2.
 2) SHT P-9 HAND DRAWN CHANGES ARE NOT
 APPROVED ON SIGNED/SEALED PLANS. RESUB-
 MIT FOR REVIEW NEW SHEETS WITH REVISION
 NUMBER AND CLOUDS. - ALSO SEE SHT P-10
 3) SHT P-9A-CU WATER HAMMER REQUIRED AT
 KITCHEN SINK FOR DISH WASHER ON HOT SIDE
 SECTION 604.9.
 4) SHTS P-10, P-16, & P-18 ARE IN PLANS
 UPSIDE DOWN. PLEASE CORRECT AND RESUBMIT
 SECTION 104.2.1.
 5) SHT P-10A-CU UNIT COMBO 16-17 PLEASE
 CLARIFY WHICH UNITS IS THIS A COMBO OF?
 CLARIFY NOTE [1], IT STATES OFFSET @
 CEILING UNDER SLAB OF 11TH LEVEL & 9TH
 LEVEL. IS THIS SHEET FOR THE 16TH & 17TH
 FLOORS? - ALSO NO HAND DRAWN CHANGES ON
 SIGNED/SEALED PLANS. SECTION 104.2.1.
 6) SHT P-11 NO HAND DRAWN CHANGES TO A
 SIGNED/SEALED SET OF PLANS. SHOW REVIS-
 ION NUMBER AND CLOUDS. SECTION 104.2.1.
 7) SHTS P-12 & P-15 NOT REVISIONS INDI-
 CATED. PLEASE CLARIFY. SECTION 104.2.1.
 8) SHT P-13 SANT. RISER #39, OFFSET VENT
 REQUIRED PER SECTION 915. SEE ATTACHED
 SHEET FOR OFFSET VENT REQUIREMENTS.
 9) VENT STACK FOR SANT. RISERS SHALL
 CONNECT AT OR BELOW LOWEST HORIZONTAL
 BRANCH AT BASE OF STACK. SEE ATTACHED
 SHEET FOR EXAMPLE. RISERS WITH VENT
 STACKS SHOW THE VENT STACK CONNECTING AT
 THE FIXTURES OF THE FIRST BRANCH. THIS
 IS NOT APPROVED. SECTION 903.4.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 - INITIALS ARE NOT ACCEPTABLE PER FBPE
 RULING. MINIMUM FIRST & LAST NAME REQ-
 UIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]