2004-06-07 00:00:00PROVISO:
 PLAN SHEET AC-1 - SMOKE EXHAUST DUCT
 FROM THE MANAGERS OFFICE THROUGH THE
 WALL INTO THE GARAGE, FIRE DAMPER IS NOT
 INDICATED.THE DUCT APPEARS TO BE 12" X
 10" THEREFORE DOES NOT FALL UNDER THE
 EXCEPTION UNDER 607.1.3, DUCT IS GREATER
 THAN 100 SQ INCHES AND SHALL HAVE NO
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 RATED WALL.PLEASE CLARIFY.
  