Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2003-08-07 00:00:00*************PROVISO********************
 1) OS&Y VALVES ARE TO BE EQUIPPED WITH
 TAMPER SWITCHES.
  
 2) THE FIRE HYDRANT CLEAR ZONE ON L-5 IS
 IS NOT CORRECT. IT ALSO USES THE WRONG
 CODE.
  
 3) THE KNOX-BOX IS TO BE INSTALLED ON
 THE OUTSIDE OF THE BUILDING.
  
 4) PRESSURE REDUCING VALES NOTED ON
 SP-12. PLEASE PROVIDE FURTHER DETAILS.
 IT IS PREFERRED THAT THEY NOT BE USED.
  
 5) AUTOMATIC DOOR RELEASE DIAGRAM.
 PLEASE SEE NFPA 101, SECTION 7.2.1.5.2.
  
 6) VARIOUS CONDUITS NOTED IN STAIR # 2.
  
 NOTES FOR MIKE CARSILLO, CAPTAIN
 805-6722 OR 835-2910
  
 NATE MCCRAY, CAPTAIN