Plan Review Notes For Permit 03020961 |
Permit Number |
03020961 |
|
Review Stop |
FIRE |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-08-07 00:00:00 | *************PROVISO******************** | | 1) OS&Y VALVES ARE TO BE EQUIPPED WITH | | TAMPER SWITCHES. | | | | 2) THE FIRE HYDRANT CLEAR ZONE ON L-5 IS | | IS NOT CORRECT. IT ALSO USES THE WRONG | | CODE. | | | | 3) THE KNOX-BOX IS TO BE INSTALLED ON | | THE OUTSIDE OF THE BUILDING. | | | | 4) PRESSURE REDUCING VALES NOTED ON | | SP-12. PLEASE PROVIDE FURTHER DETAILS. | | IT IS PREFERRED THAT THEY NOT BE USED. | | | | 5) AUTOMATIC DOOR RELEASE DIAGRAM. | | PLEASE SEE NFPA 101, SECTION 7.2.1.5.2. | | | | 6) VARIOUS CONDUITS NOTED IN STAIR # 2. | | | | NOTES FOR MIKE CARSILLO, CAPTAIN | | 805-6722 OR 835-2910 | | | | NATE MCCRAY, CAPTAIN |
|