Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2003-07-11 00:00:001) OS&Y VALVES ARE TO BE EQUIPPED WITH
 TAMPER SWITCHES.
  
 2) THE FIRE HYDRANT CLEAR ZONE ON L-5
 IS NOT CORRECT. IT ALSO USES THE WRONG
 CODE.
  
 3) THE KNOX-BOX IS TO BE INSTALLED
 ON THE OUTSIDE OF THE BUILDING.
  
 4) AN EXIT SIGN IS MISSING NEAR THE
 DOOR LEADING FROM THE PARKING GARAGE
 AND CORRIDOR ON THE GARAGE SIDE. DEAD
 ENDS SHALL NOT EXCEED 50 FEET.
  
 5) THE WEST POOL AREA DOOR LEADING
 INTO THE CORRIDOR SWINGS IN THE WRONG
 DIRECTION. DOOR SHOULD SWING IN THE
 DIRECTION OF EXIT TRAVEL. PLEASE
 REVISE AS NECESSARY.
  
 6) EXIT DOOR LEADING FROM EAST POOL
 DECK APPEARS TO SWING IN THE WRONG
 DIRECTION.
  
 7) PRESSURE REDUCING VALVES NOTED ON
 SP-12. PLEASE PROVIDE FURTHER DETAILS.
 IT IS PREFERRED THAT THEY NOT BE USED.
  
 8) AUTOMATIC DOOR RELEASE DIAGRAM.
 PLEASE SEE NFPA 101, SECTION 7.2.1.5.2.
  
 9) VARIOUS CONDUITS NOTED IN STAIR # 2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910