Plan Review Notes For Permit 03020961 |
Permit Number |
03020961 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-07-11 00:00:00 | 1) OS&Y VALVES ARE TO BE EQUIPPED WITH | | TAMPER SWITCHES. | | | | 2) THE FIRE HYDRANT CLEAR ZONE ON L-5 | | IS NOT CORRECT. IT ALSO USES THE WRONG | | CODE. | | | | 3) THE KNOX-BOX IS TO BE INSTALLED | | ON THE OUTSIDE OF THE BUILDING. | | | | 4) AN EXIT SIGN IS MISSING NEAR THE | | DOOR LEADING FROM THE PARKING GARAGE | | AND CORRIDOR ON THE GARAGE SIDE. DEAD | | ENDS SHALL NOT EXCEED 50 FEET. | | | | 5) THE WEST POOL AREA DOOR LEADING | | INTO THE CORRIDOR SWINGS IN THE WRONG | | DIRECTION. DOOR SHOULD SWING IN THE | | DIRECTION OF EXIT TRAVEL. PLEASE | | REVISE AS NECESSARY. | | | | 6) EXIT DOOR LEADING FROM EAST POOL | | DECK APPEARS TO SWING IN THE WRONG | | DIRECTION. | | | | 7) PRESSURE REDUCING VALVES NOTED ON | | SP-12. PLEASE PROVIDE FURTHER DETAILS. | | IT IS PREFERRED THAT THEY NOT BE USED. | | | | 8) AUTOMATIC DOOR RELEASE DIAGRAM. | | PLEASE SEE NFPA 101, SECTION 7.2.1.5.2. | | | | 9) VARIOUS CONDUITS NOTED IN STAIR # 2. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|