Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop P
Sequence Number 2
Notes
Date Text
2003-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW. INDICATE THE
 OPENINGS FOR THE W/C'S (WATER CLOSETS)
 PER FHA DESIGN MANUAL. (#2) SHT A5.1.08
 2) FROM PREVIOUS REVIEW. (#7) THE DRAIN
 FROM THE SPRINKLER SHALL DRAIN TO SANT.
 NOT STORM. INDIRECT WASTE INTO A FLOOR
 SINK IS REQUIRED. SHT P-2
 3) FROM PREVIOUS REVIEW. (#8) THE BACK-
 WASH FROM THE POOL FILTERS SHALL DRAIN
 TO SANITARY. SHT P-5/P-4
 4) FROM PREVIOUS REVIEW. (#9) PLEASE
 NOTE THAT THE 3" COLD WATER RISER ON SHT
 P2 IS NEXT TO THE COLUUM ON SHT P-2 AND
 P-3 BUT CHANGES TO 4" COLD WATER ON SHT
 P-4, AND CHANGES BACK TO 3" ON SHT P-5.
 4" DOMESTIC FEED IS SHOWN ON SHTS P-2, &
 P-3 BUT CHANGES TO 3" ON SHT P-4 THEN
 BACK TO 4" ON SHT P-5. PLEASE CLAIRFY.
 5) FROM PREVIOUS REVIEW. (#16) TWO AREAS
 HAVE PIPE SIZE THAT IS TOO SMALL. PLEASE
 CORRECT PIPE SIZE. SHT P-16
 6) FROM PREVIOUS REVIEW. (#17) CLEANOUTS
 REQUIRED PER 708.3.1, 708.3.3 & 708.3.4
 PLEASE SHOW ON PLANS.
 7) FROM PREVIOUS REVIEW. (#18) RELIEF
 VENTS REQUIRED IN SOIL AND WASTE STACKS
 HAVING MORE THAN 10 BRANCH INTERVALS.
 PLEASE SHOW ON RISERS.
 8) FROM PREVIOUS REVIEW. (#20) SOME
 PIPES ARE UNDERSIZED FOR THE AMOUNT OF
 FIXTURE UNITS. SEE 4" @ 251 FU & 4" @
 254 FU. SHT P-16
 9) SHT P-18 STORM BLDG DRAIN AND RISERS,
 SOME SIZES WRONG AND PIPE SIZING NOT
 SHOWN ON SOME PIPES. ALSO SQUARE FOOTAGE
 NOT SHOWN FOR GD'S. PLEASE SIZE ALL PIPE
 AND CORRECT THE SIZE FOR THOSE SECTIONS
 THAT HAVE MORE SQ FT THAN ALLOWED BY
 TABLE 1106.3 @ 4.5 INCHES PER HOUR RAIN-
 FALL.
 10) FROM PREVIOUS REVIEW. (GAS #6) SUB-
 MIT CALCULATIONS FOR COMBUSTION AIR, PER
 FBC-2001 FUEL GAS CODE SECTION 304.
 RESPONSE NOTED, BUT NO CALCULATION FOUND
 SHTS 17 OR 8.
 11) FROM PREVIOUS REVIEW. (GAS #9)
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 12) SHT P-18 PLEASE INDICATE WHICH TABLE
 FROM THE FBC-2001 GAS CODE WILL BE USED
 FOR SIZING THE GAS SYSTEM. WE HAVE NOT
 ADOPTED THE NFPA-54 CODE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692