Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop M
Sequence Number 2
Notes
Date Text
2003-05-17 00:00:00DENIED:
  
 1.PLAN SHEET AC-1, EXHAUST FROM
 BATHROOM & PARCEL RM. PENETRATING2 HR
 WALL, NO FIRE DAMPER INDICATED.
  
 2.COMMENT #4 FROM PREVIOUS REVIEW
 WAS ANSWERED IN RESPONSE LETTER BUT NOT
 CHANGED ON PLAN (AC-5 & AC-6 ELEV LOBBY)
 PLAN INDICATES A FIRE DAMPER ONLY NOT
 A COMBINATION DAMPER.PLEASE CORRECT.
  
 3.SEE COMMENTS FROM PLUMBING ON
 CALCULATIONS FOR COMBUSTION AIR.
  
 4.CONDENSING UNIT STANDS ON THE ROOF
 SHALL COMPLY WITH 2001 FBC 1511.7 FOR
 THE DISTANCE BETWEEN THE ROOF SURFACE
 & THE BOTTOM OF THE SUPPORT RAIL.
  