2003-05-16 00:00:00 | 1) THE ONE FDC NOTED NEAR THE SOUTHEAST |
| CORNER IS FACING THE WRONG DIRECTION. |
| IT SHOULD EITHER FACE 15TH STREET OR |
| NORTH FLAGLER DRIVE. THE CURRENT |
| ARRANGEMENT WILL CAUSE THE HOSE TO KINK |
| AND THUS REDUCE ITS EFFECTIVENESS. |
| |
| 2) WHAT PREVENTS A SINGLE FIRE INCIDENT |
| IN THE PARTY ROOM FROM BLOCKING BOTH |
| EXITS. |
| |
| 3) A SIGN IS REQUIRED AT ELEVATOR # 3 |
| INDICATING IT IS STRETCHER USEABLE. |
| |
| 4) THE SECURITY FEATURES PLANNED FOR THE |
| GARAGE STILL SEEM TO LEAVE THIS WRITER |
| CONFUSED WITH REGARDS TO EXITING. PLEASE |
| EXPLAIN HOW EXITING WILL WORK IN THE |
| GARAGE WHEN SECURITY DEVICES ARE |
| INSTALLED. |
| |
| 5) THE TRASH CHUTE EXHAUST ON THE ROOF |
| MUST EXTEND AT LEAST THREE FEET ABOVE |
| THE ROOF. |
| |
| 6) TACTILE SIGNAGE REQUIRED AT |
| STAIRWELLS. |
| |
| 7) PLEASE EXPLAIN THE (4) 2 1/2 X 2 1/2 |
| X 6" SIAMESE CONNECTION. HOW MANY |
| SIAMESE CONNECTIONS ARE PROPOSED. THIS |
| OFFICE WILL ONLY REQUIRED TWO OF THEM. |
| |
| 8) THE COMMERCIAL SPACES ARE TO BE FIRE |
| SPRINKLER PROTECTED AT THE TIME THE |
| BUILDING IS COMPLETED. |
| |
| 9) SEPARATE PLANS AND PERMIT REQUIRED |
| FOR ABOVE GROUND FUEL TANK. |
| |
| 10) EXIT SIGN APPEARS TO BE MISSING |
| ON SOUTH SIDE OF GUEST PARKING AREA. |
| |
| 11) EMERGENCY LIGHTING COULD NOT BE |
| LOCATED IN THE FIRE PUMP ROOM. |
| |
| 12) ARE THERE ANY EMERGENCY LIGHTS |
| PRESENT FOR STAIR # 3 AND 4. |
| |
| 13) THERE APPEARS TO BE ISSUES WITH |
| FIRE RATED DOORS AND WALLS IN SOME |
| LOCATIONS. PLEASE REVISE THE PLANS. |
| |
| 14) PLEASE ILLUSTRATE COMPLIANCE WITH |
| FBC 412.5. THE DESIGN INTENT IS NOT |
| CLEAR TO THIS WRITER AT TIME OF |
| THIS REVIEW. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |