2003-05-01 00:00:00 | ********* UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE E-1, THERE ARE FEEDER |
| /CONDUIT NOTES FOR MAINS 1 ETC. NOTES |
| MENTION SEE "NOTE 7&9?ON WHICH PAGE |
| WOULD THIS BE? |
| |
| 2)NOTE: PLEASE SEE RISER DIAGRAM AND |
| E-1. E-1 SEEMS TO SHOW MAIN #2 AS BUS |
| STAB AND RISER SHOWS CONDUIT/FEEDERS? |
| PLEASE CORRELAT/CLARIFY. |
| |
| 3)NOTE: PLEASE SEE E-1, SHOWS MULTIPLE |
| LINES COMING FROM HDP, RISER ONLY SHOWS |
| 2LINES COMING OUT AND GOING UP TO ROOF.? |
| CONDUITS THAT APPEAR TO COME FROM XDP |
| ON RISER DIAGRAM SEEM TO BE SHOWN COMING |
| FROM HDP ON E-1? PLEASE CORRELATE. PANEL |
| HB? ETC |
| 4)NOTE: PLEASE SEE E-13, IT APPEARS TO |
| SHOW FEEDERS FOR MAIN 3 COMING OVERHEAD. |
| PLEASE NOTE, AS PER LOCAL AMENDMENTS, |
| NO MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| -S ARE PERMITTED INTO BLDG. PLEASE SHOW |
| AS EITHER UNDERGROUND OR COMPLETE CONCR- |
| -ETE ENCASEMENT. 230-70 LOCAL AMEND. |
| |
| 5)NOTE: PLEASE CLARIFY FIXTURE TYPE FOR |
| ELEVATOR EQUIPMENT ROOM AND OTHER ROOMS |
| THAT REQUIRE EMERGENCY LIGHTING REQ`D TO |
| MEET 700-16? SOME OTHER LOCATIONS SHOW |
| ROOMS AND TYPE OF FIXTURES REFERENCE |
| BACK TO FIXTURE SCHEDULE.FIX SCH, DETAIL |
| -S DUAL BALLAST/BULBS. |
| |
| 6)NOTE: PLEASE SEE E-8, SHOWS RECEPT |
| ADDED TO SERVE KITCHEN COUNTER PENINSUL- |
| -AR. HOWEVER SHOWN ON LIVING ROOM CIR- |
| -CUIT? PLEASE SEE 210-11,210-52 220-16 |
| ETC. MUST BE ON W/SMALL APPLAIANCE."A-3" |
| PLEASE ALSO CLARIFY HOW THE CIRCUIT #`S |
| ARE SHOWN AS THE SAME W/ AN A&B? |
| |
| 7)NOTE: PLEASE NOTE, OCP FOR FIRE PUMP |
| TO BE PER 695-4B-1 ALSO SEE NOTE 12 |
| |
| 8)NOTE: PLEASE CLARIFY SIZE OF MAIN 4OF4 |
| FEEDS 1000A PANEL AC ON ROOF. |
| |
| 9)NOTE: PLEASE CORRELATE FEEDERS NOTED |
| ON BOTTOM OF LOAD CALCS FOR UNITS ON |
| E-8,9,10 WITH RISER DIAGRAM. RISER SHOWS |
| 3-#1'S ETC AND FEEDERS NOTED AT #2'S? |
| |
| 10)NOTE: PLEASE CLARIFY HOW POWER IS |
| TRANSFERED OVER FROM FPL TO GENERATOR |
| FOR FIRE PUMP? PLEASE ALSO SEE RISER |
| DIAGRAM, SHOWS POWER FROM FPL TO EM MAIN |
| AND THEN TO X-FER SWITCH, WHICH IS FINE, |
| HOWEVER, SHOWS POWER COMING FROM |
| GENERATOR TO EM MAIN? PLEASE CLARIFY HOW |
| THE POWER WOULD BE TRANSFERED AT THIS |
| LOCATION. HOW WOULD THIS KEEP POWER |
| BEING ON EQUIPMENT AT THE SAME TIME |
| FROM TWO DIFFERENT SOURCES W/OUT GOING |
| THROUGH TRANSFER SWITCH? |
| |
| 11)NOTE: PLEASE SEE NOTE/WIRE/CONDUIT |
| ON RISER DIAGRAM FOR FROM 1000A BRKR |
| ON GENERATOR. |
| |
| 12)NOTE: PLEASE SHOW/CLARIFY MEANS OF |
| DISC REQ`D FOR FIRE PUMP. PLEASE NOTE, |
| SHOW A MANUAL MEANS REQ`D, 225-31 |
| 230-76, 230-79, FOR DISC MEANS. |
| PLEASE CLARIFY IF THERE WILL BE A MANUAL |
| MEANS OF DISC AND/OR TRANSFER SWITCH |
| LOCATED WITH/ON SERVICE ENTRANCE RATED |
| EQUIPMENT/CONTROLLER FOR FIRE PUMP. |
| |
| 13)NOTE: PLEASE SEE GENERATOR NOTES, |
| NOTES MENTION A 600A AND 400A BRKR ON |
| GENERATOR AND ELECTRICAL RISER DIAGRAM |
| EQUIPMENT NOTES, MENTION 500A AND 1000A |
| OCP.? PLEASE CORRELATE. |
| |
| |
| PLEASE NOTE, A RESPONSE LETTER FROM |
| ELECTRICAL ENGINEER WILL HELP WITH |
| CLARIFICATIONS OF SOME COMMENTS ETC. |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. IF A MEETING ON PHONE OR |
| IN PERSON IS NEEDED, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |