2003-04-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 3/7/03:
  
 8) FBC* 104.2.1DOOR SCHEDULE.THE
 SUBMITTAL OF LEGIBLE COPIES IS NOTED.
 DOOR SCHEDULE SHEET, A8.1.01A:
 -TENANT DOOR 6B1-1 IS NOT SHOWN AS FIRE-
 RATED. SHOULD BE 20 MIN. AMEND SCHEDULE
 DOOR SCHEDULE SHEET, A8.1.01B:
 -STORAGE ROOM DOOR L1-17A IS NOT SHOWN
 RATED. SHOULD BE 1-1/2 HR. AMEND THE
 SCHEDULE.ALSO, THE DOOR REF. IS NOT
 SHOWN ON SHEET A1.2.01A. ADD REFERENCES
 -STORAGE ROOM DOOR 2.04A IS NOT SHOWN AS
 RATED. SHOULD BE 1-1/2 HR. AMEND SCHED.
 -STORAGE ROOM DOOR 3.04A IS NOT SHOWN AS
 RATED. SHOULD BE 1-1/2 HR. AMEND SCHED.
 -POOL EQUIPMENT ROOM DOOR 4.04A SHOULD
 BE LABELLED 4.01A TO MATCH PLAN SHEET
 A1.2.04A.ALSO, IT IS NOT SHOWN AS
 RATED. SHOULD BE 1-1/2 HR. AMEND SCHED.
 CHECK DOOR SCHEDULE SHEETS A8.1.01A AND
 A8.1.01B TO ENSURE THAT ALL DOORS ARE
 SHOWN AS FIRE-RATED WHERE REQUIRED, AS
 THIS REVIEW IS NOT EXHAUSTIVE.
  
 11) INCORRECT REFERENCE TO BUILDING
 OCCUPANCY GROUP 'R4' (RESIDENTIAL CARE/
 ASSISTED LIVING).SHEET G3 STILL REFERS
 TO OCCUPANCY GROUP 'R4', UNDER THE
 HEADING 'CODE DATA'.AMEND THE PLAN.
  
 12) FBC 412.10.1 SPRINKLER DESIGN
 PARAMETERS.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.SHEET LS0.01
 'GENERAL INFORMATION' STILL REFERS TO
 FBC 412.1.10.THIS SHOULD BE CORRECTED
 TO READ FBC 412.10.1
  
 13) INFORMATIVE: FBC TABLE 600THE
 ADDITION OF THE TABLE 600 INFORMATION TO
 SHEET LS1.02 IS NOTED.CODE REFERENCES
 AND FOOTNOTE REFERENCES PERTAINING TO
 CONSTRUCTION TYPES II, III AND IV HAVE
 BEEN INADVERTENTLY INTERSPERSED WITH THE
 TYPE I INFORMATION.THE CORRECTIONS
 HAVE BEEN RED-LINED ON ONE (NOT ALL) OF
 THE SUBMITTED COPIES.
  
 14) SHEET A1.2.02A.STAIR #1 IS MIS-
 LABELLED AS STAIR #2.CONTRARY TO THE
 SUBMITTED COMMENT RESPONSE MEMO, THIS
 COMMENT HAS NOT BEEN ADDRESSED.
  
 15) FBC 1005.6.5SMOKEPROOF ENCLOSURE.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.SHEET A1.2.01 SHOWS WALL
 TYPE B11 (WHICH IS ONLY ONE-HOUR RATED)
 ON TWO OF THE WALLS SEPARATING SERVICE
 CORRIDOR 1-10 AND RESTROOM 1-01.AMEND
 THE PLANS TO SHOW 2-HOUR FIRE-RATED
 WALLS.
  
 18) FBC TABLE 704.1SHEET 1.01.
 SEPARATION.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.THE PLAN DOES NOT
 SHOW THE REQUIRED ONE-HOUR FIRE-RATED
 SEPARATION BETWEEN THE FUTURE RETAIL
 (AND THE FUTURE OFFICE) OCCUPANCY AND
 THE ADJACENT CORRIDOR.AMEND THE PLAN.
  
 20) FBC 704.1THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.SHEET LS1.02 STILL
 DOES NOT SHOW ANY FIRE-RATING FOR THE
 WALLS BETWEEN THE VEHICLE RAMP (ALSO THE
 ACCESSIBLE PARKING SPACE OPPOSITE) AND
 THE 'VOID' ABOVE THE FIRST FLOOR
 RECEPTION, MAIL ROOM AND STORAGE ROOM.
  
 21) FBC TABLE 1003.1SHEET LS1.05.THE
 SUBMITTED RESPONSE IS NOTED. SUBTRACTION
 OF THE BAR AREA TO CALCULATE THE FOOR
 AREA IS ACCEPTABLE, BUT THE 5'
 'CIRCULATION PATH' SHALL NOT BE EXCLUDED
 FROM THE FLOOR AREA CALCULATION.AMEND
 THE CALCULATION.
  
 23) FBC 1005.6.2STAIR #1 AND ADJACENT
 SHAFTS AND ELEVATORS.THIS COMMENT HAS
 NOT BEEN PROPERLY ADDRESSED.SHEETS
 LS1.05 AND LS1.06 STILL SHOW ONLY ONE-
 HOUR FIRE SEPARATION BETWEEN THE EXIT
 ACCESS CORRIDOR AND THE STAIRWAY/SHAFT/
 ELEVATOR.AMEND THE PLANS TO SHOW THE
 REQUIRED 2-HOUR SEPARATION.
  
 25) FBC 301.2OCCUPANT LOAD TABLE,
 SHEET LS1.06.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.THE REVISED AREA OF
 'RESIDENTIAL' OCCUPANCY IS STATED AS
 16544 GSF.IT IS ACTUALLY IN EXCESS OF
 18000 GSF FOR EACH OF THE TYPICAL FLOORS
 AMEND THE TABLE.
  
 26) FBC TABLE 705.1.2THIS COMMENT HAS
 NOT BEEN ADDRESSED.SHEET LS1.06 STILL
 SHOWS NO FIRE-RATING FOR THE WALLS
 BETWEEN STAIR #1 AND THE ADJACENT SHAFTS
 OR FOR WALLS BETWEEN INDIVIDUAL SHAFTS.
 ALSO, THE WALL BETWEEN STAIR #2 LOBBY
 AND THE ADJACENT ELEVATOR LOBBY
 (FBC 412.6.1) IS NOT SHOWN AS FIRE-RATED
 AMEND THE PLANS.
  
 31) THE SUBMITTED MODIFIED BITUMEN ROOF
 SYSTEM PRODUCT APPROVAL NOA# 02-0605.04
 STATES A MAX.DESIGN PRESSURE OF
 -112.5 PSF WHICH IS LESS THAN THE
 -140 PSF PEAK NEGATIVE PRESSURE STATED
 ON SHEET S-21.ALSO, THE SYSTEM THAT
 ACHIEVES -112.5 PSF IS FOR APPLICATION
 TO STEEL DECK AND THEREFOR NOT
 APPLICABLE TO THE PROPOSED CONCRETE ROOF
 DECKS.SUBMIT AN ALTERNATIVE PRODUCT
 APPROVAL.BEFORE SUBMITTAL, THE
 ALTERNATIVE PRODUCT APPROVAL SHALL BE
 REVIEWED BY THE ENGINEER-OF-RECORD AND
 THE PROPOSED ASSEMBLY/SYSTEM SHALL BE
 CIRCLED ON EACH COPY.
  
 32) FBC 1606.1.4SUBMIT PRODUCT
 APPROVALS FOR THE WINDOWS AND EXTERIOR
 DOORS.
  
 34) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORMS.THE PROJECT INFORMATION HAS NOT
 BEEN ENTERED PROPERLY.THE ARCHITECT'S
 REGISTRATION NUMBER SHALL BE ENTERED ON
 SHEET 2 OF THE FORMS.
  
 35) FBC 411.2.3PARKING GARAGE BARRIER.
 AN IMPACT GUARDRAIL NOTE HAS BEEN ADDED
 TO SHEET A1.1.02 (LEVEL 2 PARKING PLAN),
 UNDER 'GENERAL NOTES'.ALL OF THE
 'GENERAL NOTES' EXCEPT THE IMPACT
 GUARDRAIL NOTE, HAVE BEEN REPEATED ON
 SHEET A1.1.03 AND 04 (LEVEL 3 PARKING
 AND LEVEL 4 PARKING PLAN).SHEETS S-3
 THRU S-8 STILL DO NOT SHOW ANY VEHICULAR
 IMPACT BARRIER DETAILS FOR THE WALLS AT
 THE END OF THE PERIMETER PARKING SPACES.
 PROVIDE IMPACT GUARDRAIL/WALL DETAILS.
  
 36) FBC 1608.2GUARDRAIL STRENGTH.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE AMENDED NOTES ON
 SHEET A6.1.05, 06 AND 07 DO NOT STATE
 THE REQUIREMENT FOR THE GUARDRAIL
 SYSTEMS TO BE DESIGNED AND CONSTRUCTED
 FOR A CONCENTRATED LOAD OF 200 LB
 APPLIED AT ANY POINT AND IN ANY
 DIRECTION AT THE TOP OF THE GUARDRAIL.
 ADD THIS REQUIREMENT TO THE NOTES.
 ALL OF THE GUARDRAIL NOTES SHALL BE
 ADDED TO SHEET A7.1.05 'RAILING DETAILS'
  
 37) FBC 1608.2.1HANDRAIL STRENGTH.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 CONTRARY TO THE SUBMITTED COMMENT
 RESPONSE MEMO, SHEET A6.1.08, DETAIL 5
 STILL REFERS TO SFBC (SOUTH FLORIDA
 BUILDING CODE) FOR HANDRAIL STRENGTH
 REQUIREMENTS.THAT CODE IS NOT
 APPLICABLE.THE RELEVANT CODE
 REQUIREMENTS ARE IN FLORIDA BUILDING
 CODE (2001) FBC 1608.2.1.AMEND THE
 PLAN.
  
 42) FBC 11-4.13.6MANEUVERING
 CLEARANCES AT DOORS.THIS COMMENT HAS
 NOT BEEN ADDRESSED. THE SUBMITTED
 COMMENT RESPONSE MEMO REFERS TO 'SHEETS
 A1.105A AND A1.105B'.THESE SHEETS
 NUMBERS ARE NOT PART OF THE SUBMITTED
 PLANS SETS.THE COMMENT RESPONSE MEMO
 SHOULD REFER TO SHEETS A1.2.05A AND
 A1.2.05B.THESE PLANS DO NOT GIVE ANY
 DIMENSIONS FOR THE LOCATIONS IN QUESTION
 AMEND THE PLANS TO PROVIDE/CONFIRM THE
 REQUIRED 12" CLEARANCE BETWEEN THE DOOR
 FRAME AND THE ADJACENT WALL ON THE PUSH
 SIDE OF MEN'S RESTROOM DOOR 5-06 IF THE
 DOOR HAS BOTH A CLOSER AND A LATCH.
 ALSO AMEND THE PLANS TO PROVIDE/CONFIRM
 THE REQUIRED 18" CLEARANCE BETWEEN THE
 LEADING EDGE OF THE DOOR AND THE
 ADJACENT WALL ON THE PULL SIDE OF THE
 WOMEN'S RESTROOM DOOR 5-08.
 NOTE: ENSURE THAT THE REQUIRED CLEARANCE
 IS ALSO PROVIDED AT THE DOORS FROM
 CORRIDOR 5-11 TO THE EAST POOL DECK AND
 TO THE WEST POOL DECK.
  
 THE FOLLOWING ARE ADDITIONAL COMMENTS
 ARISING FROM REVIEW OF THE REVISED
 PLANS AND APPLICATION FOR PERMIT:
  
 46) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 47) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH DEPARTMENT
 OF CONSTRUCTION SERVICES BEFORE A
 BUILDING PERMIT CAN BE ISSUED.
  
 48) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES THE BOUNDARY LINES BETWEEN
 FOUR DIFFERENT LOTS.SUBMIT A COPY OF A
 RECORDED UNITIVE TITLE DOCUMENT SO THAT
 FBC TABLE 600 BOUNDARY LINE REQUIREMENTS
 MAY BE DEEMED NOT APPLICABLE.
  
 49) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 50) FBC TABLE 600SHEET A1.1.01.THE
 ADDITION OF THE 'FIRE RESISTANCE RATING
 CALCULATIONS' TABLE IS NOTED.FOR THE
 WEST ELEVATION OF THE PODIUM, THE TABLE
 STATES THAT THE PERMITTED PERCENTAGE OF
 UNPROTECTED OPENINGS IS 40%.AS THE
 DISTANCE TO THE PROPERTY LINE IS BETWEEN
 10 FT AND 20 FT (ACTUALLY 16'-6") THE
 PERMITTED PERCENTAGE OF OPENINGS, FROM
 TABLE 600, IS 20%.AMEND THE FIRE
 RESISTANCE RATING CALCULATION TABLE.IT
 IS, ANY CASE, NOTED THAT THE PERCENTAGE
 OF UNPROTECTED OPENINGS IN THE PODIUM
 WEST ELEVATION IS 18% AND SO DOES NOT
 EXCEED THAT PERMITTED.
  
 51) FBC 11-4.9.4SHEET A6.1.08.AT THE
 TOP OF THE PARKING LOT STAIR, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12" BEYOND THE TOP RISER.AT THE
 BOTTOM OF THE STAIR, HANDRAILS SHALL
 CONTINUE TO SLOPE, BEYOND THE BOTTOM
 RISER FOR A DISTANCE EQUAL TO THE WIDTH
 OF ONE RISER AND THEN EXTEND
 HORIZONTALLY FOR A FURTHER 12 INCHES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]