2005-01-10 00:00:00 | REVISION - DENIED |
| FOR SHEETS P-3, P-8, P-8, P-9, P-10, |
| P-11, P-12, P-13, P-15, &P-16. |
| |
| 1) SHT P-3 NO CHANGES SHOWN FROM |
| REVISION SEALED 07/29/04 AND REVIEWED ON |
| 08/14/04. PLEASE CLAIRFY. SECTION |
| 104.2.1. |
| 2) SHT P-8 FLOOR SINK TO BE LOCATED SO |
| PIPING FROM RVD SHALL NOT PRESENT A |
| TRIPPING HAZARD. |
| 3) SHTS P-9 & P-10 NO CHANGES SHOWN FROM |
| ORIGINAL STAMPED SHEET SEALED 07/08/03 |
| AND ISSUED 08/07/03. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| 4) SHTS P-11 & P-12 NO CHANGES SHOWN |
| FROM REVISION SEALED 06/28/04, REVIEWED |
| 08/14/04. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| 5) SHT P-13 MANY RISERS SHOW REVISION |
| NUMBERS 6 & 10 AND CLOUDED AT THE BASE |
| OF THE RISERS, BUT NO CHANGES ARE SHOWN |
| ARE SHOWN. PLEASE CLAIRFY. SECTION |
| 104.2.1. - SANT. RISER #1, OFFSET VENT |
| REQUIRED BETWEEN 5TH & 6TH FLOORS. |
| SECTION 915.1. - SANT. RISER #17, |
| HORIZONTAL DRY VENT NOT APPROVED. |
| SECTION 905.3. |
| 6) SHTS P-15 & P-16 NO CHANGES SHOWN |
| FROM REVISION SEALED 08/20/04 AND |
| REVIEWED 10/06/04. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| |
| FOLLOWING SHEETS REVISIONS APPROVED. - |
| P-2, P-5, P-6, P-9A-CU, P-10A-CU, P-17, |
| & P-18 |
| |
| |
| |