Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop P
Sequence Number 12
Notes
Date Text
2005-01-10 00:00:00REVISION - DENIED
 FOR SHEETS P-3, P-8, P-8, P-9, P-10,
 P-11, P-12, P-13, P-15, &P-16.
  
 1) SHT P-3 NO CHANGES SHOWN FROM
 REVISION SEALED 07/29/04 AND REVIEWED ON
 08/14/04. PLEASE CLAIRFY. SECTION
 104.2.1.
 2) SHT P-8 FLOOR SINK TO BE LOCATED SO
 PIPING FROM RVD SHALL NOT PRESENT A
 TRIPPING HAZARD.
 3) SHTS P-9 & P-10 NO CHANGES SHOWN FROM
 ORIGINAL STAMPED SHEET SEALED 07/08/03
 AND ISSUED 08/07/03. PLEASE CLARIFY.
 SECTION 104.2.1.
 4) SHTS P-11 & P-12 NO CHANGES SHOWN
 FROM REVISION SEALED 06/28/04, REVIEWED
 08/14/04. PLEASE CLARIFY. SECTION
 104.2.1.
 5) SHT P-13 MANY RISERS SHOW REVISION
 NUMBERS 6 & 10 AND CLOUDED AT THE BASE
 OF THE RISERS, BUT NO CHANGES ARE SHOWN
 ARE SHOWN. PLEASE CLAIRFY. SECTION
 104.2.1. - SANT. RISER #1, OFFSET VENT
 REQUIRED BETWEEN 5TH & 6TH FLOORS.
 SECTION 915.1. - SANT. RISER #17,
 HORIZONTAL DRY VENT NOT APPROVED.
 SECTION 905.3.
 6) SHTS P-15 & P-16 NO CHANGES SHOWN
 FROM REVISION SEALED 08/20/04 AND
 REVIEWED 10/06/04. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 FOLLOWING SHEETS REVISIONS APPROVED. -
 P-2, P-5, P-6, P-9A-CU, P-10A-CU, P-17,
 & P-18
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]