2003-03-11 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS FOR
 THE COMMON AREAS, PER 2001 FBC(M) TABLE
 403.3.
  
 2.PROVIDE OUTSIDE A CALCULATIONS FOR
 THE RESIDENTIAL AREAS BY MEANS OF
 NATURAL VENTILATION (2001 FBC(M) 402.2)
 OR MECHANICAL (2001 FBC(M) TABLE 403.3).
  
 3.SMOKE EVAC IS INDICATED FOR THE
 LOBBY & COMMON AREAS.INDICATE WHAT
 WILL BE DONE FOR THE CORRIDOR EXITS IN
 RESIDENTIAL AREAS.SHOW COMPLIANCE WITH
 2001 FBC 412.5.
  
 4.PLAN SHEETS AC-5 & AC-6 - SUPPLY
 PENETRATION AT ELEVATOR LOBBY INDICATES
 A FIRE DAMPER ONLY.PLEASE CLARIFY,
 SHOULD THIS BE A FIRE/SMOKE DAMPER?
  
 5.PLAN SHEET AC-5 PENETRATION TO P/A 4
 MISSING FIRE/SMOKE DAMPER ALSO.
  
 6.MECHANICAL PLANS INDICATE IN-LINE
 BOOSTER FANS FOR THE DRYERS.PROVIDE
 SUBMITTAL FOR THE IN-LINE FAN.INDICATE
 IF ANY PRECAUTIONS ARE TO BE TAKEN
 SHOULD THE FAN FAIL (I.E. ALARM OR SOME
 TYPE OF NOTIFICATION).
  
 7.PROVIDE ENERGY & MANUAL J CALCS AS
 PER 2001 FBC CHAPTER 13.
  
 8.AS PER FAIR HOUSING GUIDELINES THE
 ENVIRONMENTAL CONTROLAS SHALL BE
 POSITIONED IN ACCESSIBLE LOCATIONS.
 HEIGHT REQUIREMENT SHALL BE A MINIMUM
 OF 15" A.F.F. & MAXIMUM OF 48" A.F.F..
  
 9.PROVIDE SEQUENCE OF OPERATION FOR
 ALL AREAS EVAC AS WELL AS SMOKE CONTROL.
 SHOW COMPLIANCE WITH 2001 FBC 412.5
  