2003-03-11 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| FOR REVIEW. |
| |
| 1.PROVIDE OUTSIDE AIR CALCULATIONS FOR |
| THE COMMON AREAS, PER 2001 FBC(M) TABLE |
| 403.3. |
| |
| 2.PROVIDE OUTSIDE A CALCULATIONS FOR |
| THE RESIDENTIAL AREAS BY MEANS OF |
| NATURAL VENTILATION (2001 FBC(M) 402.2) |
| OR MECHANICAL (2001 FBC(M) TABLE 403.3). |
| |
| 3.SMOKE EVAC IS INDICATED FOR THE |
| LOBBY & COMMON AREAS.INDICATE WHAT |
| WILL BE DONE FOR THE CORRIDOR EXITS IN |
| RESIDENTIAL AREAS.SHOW COMPLIANCE WITH |
| 2001 FBC 412.5. |
| |
| 4.PLAN SHEETS AC-5 & AC-6 - SUPPLY |
| PENETRATION AT ELEVATOR LOBBY INDICATES |
| A FIRE DAMPER ONLY.PLEASE CLARIFY, |
| SHOULD THIS BE A FIRE/SMOKE DAMPER? |
| |
| 5.PLAN SHEET AC-5 PENETRATION TO P/A 4 |
| MISSING FIRE/SMOKE DAMPER ALSO. |
| |
| 6.MECHANICAL PLANS INDICATE IN-LINE |
| BOOSTER FANS FOR THE DRYERS.PROVIDE |
| SUBMITTAL FOR THE IN-LINE FAN.INDICATE |
| IF ANY PRECAUTIONS ARE TO BE TAKEN |
| SHOULD THE FAN FAIL (I.E. ALARM OR SOME |
| TYPE OF NOTIFICATION). |
| |
| 7.PROVIDE ENERGY & MANUAL J CALCS AS |
| PER 2001 FBC CHAPTER 13. |
| |
| 8.AS PER FAIR HOUSING GUIDELINES THE |
| ENVIRONMENTAL CONTROLAS SHALL BE |
| POSITIONED IN ACCESSIBLE LOCATIONS. |
| HEIGHT REQUIREMENT SHALL BE A MINIMUM |
| OF 15" A.F.F. & MAXIMUM OF 48" A.F.F.. |
| |
| 9.PROVIDE SEQUENCE OF OPERATION FOR |
| ALL AREAS EVAC AS WELL AS SMOKE CONTROL. |
| SHOW COMPLIANCE WITH 2001 FBC 412.5 |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |