Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-02-20 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT.
  
 3) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 4) ALL CONSTRUCTION, DEMOLITION, AND
 RENOVATION WORK TO COMPLY WITH NFPA
 241.
  
 5) ELECTRONIC TAMPER SWITCHES, A CHAIN
 AND LOCK ARE REQUIRED ON THE FIRE LINE
 BACKFLOW DEVICE.
  
 6) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED FOR THE BUILDING.
  
 7) THE PARKING GARAGE IS TO BE SEPARATED
 BY AT LEAST A TWO HOUR FIRE RATING.
  
 8) STAIR IDENTIFICATION SIGNS ARE
 REQUIRED.
  
 9) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE MARKED
 "SHAFTWAY" IN RED LETTERS.
  
 10) PLEASE REVIEW SECTION 412.4.3 OF
 THE FBC,"FIRE COMMAND CENTER", TO ENSURE
 ALL REQUIRED EQUIPMENT IS CONTAINED
 WITHIN.
  
 11) QUICK RESPONSE OR LISTED
 RESIDENTIAL FIRE SPRINKLER HEADS ARE
 TO BE USED.
  
 12) PLEASE INDICATE WHICH ELEVATORS
 COMPLY WITH THE FBC, SECTION 3003.4
 "STRETCHER REQUIREMENTS".
  
 13) PLEASE SHOW SIGNAGE "IN A FIRE
 EMERGENCY, DO NOT USE ELEVATOR". USE
 EXIT STAIRS" IN ACCORDANCE WITH FBC,
 SECTION 3003.3.
  
 14) SHEET P-1 INDICATES A 6" FIRE LINE
 BUT OTHER SHEETS DISPLAY AN 8" LINE.
 IF THE FIRE PUMP IS 1000 GPM, THEN AN
 8" LINE IS THE MINIMUM SIZE. PLEASE
 CORRECT DISCREPANCY.
  
 15) PLEASE INDICATE ON THE PLANS, WHAT
 THE VOICE EVACUATION MESSAGE WILL SAY
 FOR THE FIRE ALARM SYSTEM.
  
 16) THE BUILDING ADDRESS SIGN SHOWN ON
 A3.1.01 SHALL HAVE AT LEAST 6" NUMERALS.
  
 17) PLEASE INDICATE COMPLIANCE WITH
 FBC,SECTION 412.5, "SMOKE CONTROL".
  
 18) PLANS MAKE REFERENCE TO NFPA 13R.
 NFPA 13R IS NOT APPLICABLE TO THIS
 PROJECT.
  
 19) SECURITY GATES SHOWN IN THE GARAGE.
 HOW DOES THESE DEVICES RESTRICT
 EXITING.
  
 20) HOW DOES PERSONS EXIT VIA THE
 VEHICLE INGRESS AND EGRESS POINTS OF
 THE GARAGE.
  
 21) INCOMPLETE LOCKING DEVICE NOTES ON
 PAGE LS1.02.
  
 22) THE TWO EXITS SHOWN IN THE PARTY
 ROOM ARE NOT PROPERLY SEPARATED FROM
 ONE ANOTHER.
  
 23) SEVERAL DOORS ON LEVEL 5 NEAR STAIR
 # 1 OPEN OUTWARD IN CLOSE PROXIMITY TO
 ONE ANOTHER.
  
 24) SOME 20 MINUTE OR OTHER SYMBOLS
 ARE MISSING NEAR ELEVATOR LOBBY NEAR
 STAIR # 1.
  
 25) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR METAL GUARDRAILS
 MOUNTED ABOVE CRASH WALL.
  
 26) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR TEMPERED GLASS
 RAILING NOTED ON PAGE A1.1.05.
  
 27) ALL RAMPS AND STAIRS TO HAVE
 HANDRAILS.
  
 28) ALL FABRIC AWNINGS ARE TO BE FIRE
 RETARDANT.
  
 29) DOOR SCHEDULE DIFFICULT TO READ.
  
 30) AN EXIT SIGN APPEARS TO BE MISSING
 FROM GUEST PARKING.
  
 31) PLEASE CLEARLY IDENTIFY ALL
 EMERGENCY LIGHTS.
  
 32) ARE EMERGENCY LIGHTS PRESENT IN
 THE STAIRTOWERS. THE SYSMBOL USED DOES
 NOT SUGGEST THAT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL