Date |
Text |
2003-02-20 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| TO, DURING AND AFTER CONSTRUCTION. |
| |
| 2) SUITABLE ROADS ARE TO BE PROVIDED |
| FOR FIRE AND PARAMEDICAL EQUIPMENT. |
| |
| 3) TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN THE BUILDING REACHES THREE STORIES |
| OR THIRTY FEET IN HEIGHT. |
| |
| 4) ALL CONSTRUCTION, DEMOLITION, AND |
| RENOVATION WORK TO COMPLY WITH NFPA |
| 241. |
| |
| 5) ELECTRONIC TAMPER SWITCHES, A CHAIN |
| AND LOCK ARE REQUIRED ON THE FIRE LINE |
| BACKFLOW DEVICE. |
| |
| 6) A KNOX-BOX RAPID ENTRY SYSTEM WILL |
| BE REQUIRED FOR THE BUILDING. |
| |
| 7) THE PARKING GARAGE IS TO BE SEPARATED |
| BY AT LEAST A TWO HOUR FIRE RATING. |
| |
| 8) STAIR IDENTIFICATION SIGNS ARE |
| REQUIRED. |
| |
| 9) ALL SHAFTS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE MARKED |
| "SHAFTWAY" IN RED LETTERS. |
| |
| 10) PLEASE REVIEW SECTION 412.4.3 OF |
| THE FBC,"FIRE COMMAND CENTER", TO ENSURE |
| ALL REQUIRED EQUIPMENT IS CONTAINED |
| WITHIN. |
| |
| 11) QUICK RESPONSE OR LISTED |
| RESIDENTIAL FIRE SPRINKLER HEADS ARE |
| TO BE USED. |
| |
| 12) PLEASE INDICATE WHICH ELEVATORS |
| COMPLY WITH THE FBC, SECTION 3003.4 |
| "STRETCHER REQUIREMENTS". |
| |
| 13) PLEASE SHOW SIGNAGE "IN A FIRE |
| EMERGENCY, DO NOT USE ELEVATOR". USE |
| EXIT STAIRS" IN ACCORDANCE WITH FBC, |
| SECTION 3003.3. |
| |
| 14) SHEET P-1 INDICATES A 6" FIRE LINE |
| BUT OTHER SHEETS DISPLAY AN 8" LINE. |
| IF THE FIRE PUMP IS 1000 GPM, THEN AN |
| 8" LINE IS THE MINIMUM SIZE. PLEASE |
| CORRECT DISCREPANCY. |
| |
| 15) PLEASE INDICATE ON THE PLANS, WHAT |
| THE VOICE EVACUATION MESSAGE WILL SAY |
| FOR THE FIRE ALARM SYSTEM. |
| |
| 16) THE BUILDING ADDRESS SIGN SHOWN ON |
| A3.1.01 SHALL HAVE AT LEAST 6" NUMERALS. |
| |
| 17) PLEASE INDICATE COMPLIANCE WITH |
| FBC,SECTION 412.5, "SMOKE CONTROL". |
| |
| 18) PLANS MAKE REFERENCE TO NFPA 13R. |
| NFPA 13R IS NOT APPLICABLE TO THIS |
| PROJECT. |
| |
| 19) SECURITY GATES SHOWN IN THE GARAGE. |
| HOW DOES THESE DEVICES RESTRICT |
| EXITING. |
| |
| 20) HOW DOES PERSONS EXIT VIA THE |
| VEHICLE INGRESS AND EGRESS POINTS OF |
| THE GARAGE. |
| |
| 21) INCOMPLETE LOCKING DEVICE NOTES ON |
| PAGE LS1.02. |
| |
| 22) THE TWO EXITS SHOWN IN THE PARTY |
| ROOM ARE NOT PROPERLY SEPARATED FROM |
| ONE ANOTHER. |
| |
| 23) SEVERAL DOORS ON LEVEL 5 NEAR STAIR |
| # 1 OPEN OUTWARD IN CLOSE PROXIMITY TO |
| ONE ANOTHER. |
| |
| 24) SOME 20 MINUTE OR OTHER SYMBOLS |
| ARE MISSING NEAR ELEVATOR LOBBY NEAR |
| STAIR # 1. |
| |
| 25) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR METAL GUARDRAILS |
| MOUNTED ABOVE CRASH WALL. |
| |
| 26) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| REQUIREMENTS FOR TEMPERED GLASS |
| RAILING NOTED ON PAGE A1.1.05. |
| |
| 27) ALL RAMPS AND STAIRS TO HAVE |
| HANDRAILS. |
| |
| 28) ALL FABRIC AWNINGS ARE TO BE FIRE |
| RETARDANT. |
| |
| 29) DOOR SCHEDULE DIFFICULT TO READ. |
| |
| 30) AN EXIT SIGN APPEARS TO BE MISSING |
| FROM GUEST PARKING. |
| |
| 31) PLEASE CLEARLY IDENTIFY ALL |
| EMERGENCY LIGHTS. |
| |
| 32) ARE EMERGENCY LIGHTS PRESENT IN |
| THE STAIRTOWERS. THE SYSMBOL USED DOES |
| NOT SUGGEST THAT. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 659-8096,EXT.8497 |
| 835-2910 |