Plan Review Notes
Plan Review Notes For Permit 03020961
Permit Number 03020961
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-03 00:00:00********** UNSAT ******************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL DRAWINGS.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 ALL SHEETS. EACH PARKING LEVEL AND OTHER
 SHEETS MISSING CIRCUIT #`S.
  
 3)NOTE: PLEASE CLARIFY TWO DIFFERENT
 POOL EQUIPMENT ROOMS?E-4 PLEASE CALRIFY
 IF THERE IS MORE THANONE POOL?
  
 4)NOTE: PLEASE CLARIFY EM LTS FOR
 BATHS LEVEL 5 AMENITIES.
  
 5)NOTE: PLEASE NOTE ON E-8, SD`S TO BE
 5' FROM RA'S PER MANFACT. SPECS
  
 6)NOTE: PLEASE SEEMASTER BATHS, GFI'S
 3'MIN FROM SINK. 210-52D
  
 7)NOTE: PLEASE SEE MISSING PENINSULAR
 RECEPTS ON VARIOUS UNITS. 210-52-C-3,4
  
 8)NOTE: PLEASE COMPLETE PANEL SCHEULES,
 SHOWN AS BLANKS STARTING ON E-12??
  
 9)NOTE: PLEASE COMPLETE RISER DIAGRAM
 FOR A COMPLETE REVIEW TO BE PERFORMED.
 PLEASE NOTE, THERE MAY BE OTHER COMMENTS
 TO FOLLOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372