Plan Review Notes For Permit 03020961 |
Permit Number |
03020961 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-03-03 00:00:00 | ********** UNSAT ****************** | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | THAT WILL AFFECT ELECTRICAL DRAWINGS. | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | ALL SHEETS. EACH PARKING LEVEL AND OTHER | | SHEETS MISSING CIRCUIT #`S. | | | | 3)NOTE: PLEASE CLARIFY TWO DIFFERENT | | POOL EQUIPMENT ROOMS?E-4 PLEASE CALRIFY | | IF THERE IS MORE THANONE POOL? | | | | 4)NOTE: PLEASE CLARIFY EM LTS FOR | | BATHS LEVEL 5 AMENITIES. | | | | 5)NOTE: PLEASE NOTE ON E-8, SD`S TO BE | | 5' FROM RA'S PER MANFACT. SPECS | | | | 6)NOTE: PLEASE SEEMASTER BATHS, GFI'S | | 3'MIN FROM SINK. 210-52D | | | | 7)NOTE: PLEASE SEE MISSING PENINSULAR | | RECEPTS ON VARIOUS UNITS. 210-52-C-3,4 | | | | 8)NOTE: PLEASE COMPLETE PANEL SCHEULES, | | SHOWN AS BLANKS STARTING ON E-12?? | | | | 9)NOTE: PLEASE COMPLETE RISER DIAGRAM | | FOR A COMPLETE REVIEW TO BE PERFORMED. | | PLEASE NOTE, THERE MAY BE OTHER COMMENTS | | TO FOLLOW. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|