Plan Review Notes
Plan Review Notes For Permit 03020790
Permit Number 03020790
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-06 00:00:00********* NOTES/PROVISO******
  
 1)NOTE: PLEASE CORRELATE OCP AND AWG
 FOR AHU #2. SHOW 2P-60A ON#10.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 A EXT PANEL AND NO PANEL SCHEDULE IS
 SUBMITTED. RISER SHOWS ITEMS FROM EXT
 PANEL AND DOES NOT LIST ANY OCP .
  
 3)NOTE: PLEASE SEE MISSING RECEPT
 UPSTAIRS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372