Plan Review Notes
Plan Review Notes For Permit 03020782
Permit Number 03020782
Review Stop E
Sequence Number 1
Notes
Date Text
2003-03-05 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE MISSING DISC REQ`D
 FOR A/C COND UNIT. 440-11
  
 2)NOTE: PLEASE SEE SIZE OF WIRE SHOWN
 FOR SUB PANEL, ON A 2P60A BRKR. PLEASE
 CORRELATE AWG W/ OCP.
  
 3)NOTE: PLEASE ALSO SEE LOAD CALCULATION
 -S, FOR SUB PANEL, THEY DO NOT SEEM TO
 CORRELATE WITH WHAT IS SHOWN. PLEASE
 VERIFY LOADING OF 60A BRKR AT NO MORE
 THAN 80%?
  
 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12
  
 5)NOTE: PLEASE LIST THE REQ`D BATH
 CIRCUIT(S) PER 210-52D/210-11-C3.
 MUST BE 20A #12. SHOWN FOR GUEST HOUSE
 AS #14. 15A AND ALSO FOR MAIN HOUSE.
  
 6)NOTE: PLEASE SEE RECEPT SPACING FOR
 KITCHEN COUNTERSPACE. PER 210-52-C-1
  
 7)NOTE: PLEASE SEE MAX OCP FOR COND UNIT
 SHOWN AS 5KW., SHOWS 2P50A BRKR?
  
 8)NOTE: PLEASE SEE SMALL APPLIANCE
 CIRCUITS, SHOWS 2 CIRCUITS AND LOAD FOR
 THREE??
  
 9)NOTE: PLEASE SEE WRONG NEC ART REF.
 FROM 96 NEC, 250-95 SHOULD BE 250-122.
  
 10)NOTE: PLEASE SEE ALL ROOM DESIGNATION
 -S ARE MISSING ON FLOOR PLAN? PLEASE
 SHOW.
  
 11)NOTE: PLEASE MOVE SDIN GUESTHOUSE,
 TO BE IN IMEDIATE VICINITY OF STAIRS
 LEADING TO SECOND FLOOR. NFPA-72
 2-5.2.1.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372