2003-03-05 00:00:00 | *************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE MISSING DISC REQ`D |
| FOR A/C COND UNIT. 440-11 |
| |
| 2)NOTE: PLEASE SEE SIZE OF WIRE SHOWN |
| FOR SUB PANEL, ON A 2P60A BRKR. PLEASE |
| CORRELATE AWG W/ OCP. |
| |
| 3)NOTE: PLEASE ALSO SEE LOAD CALCULATION |
| -S, FOR SUB PANEL, THEY DO NOT SEEM TO |
| CORRELATE WITH WHAT IS SHOWN. PLEASE |
| VERIFY LOADING OF 60A BRKR AT NO MORE |
| THAN 80%? |
| |
| 4)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS PER 210-12 |
| |
| 5)NOTE: PLEASE LIST THE REQ`D BATH |
| CIRCUIT(S) PER 210-52D/210-11-C3. |
| MUST BE 20A #12. SHOWN FOR GUEST HOUSE |
| AS #14. 15A AND ALSO FOR MAIN HOUSE. |
| |
| 6)NOTE: PLEASE SEE RECEPT SPACING FOR |
| KITCHEN COUNTERSPACE. PER 210-52-C-1 |
| |
| 7)NOTE: PLEASE SEE MAX OCP FOR COND UNIT |
| SHOWN AS 5KW., SHOWS 2P50A BRKR? |
| |
| 8)NOTE: PLEASE SEE SMALL APPLIANCE |
| CIRCUITS, SHOWS 2 CIRCUITS AND LOAD FOR |
| THREE?? |
| |
| 9)NOTE: PLEASE SEE WRONG NEC ART REF. |
| FROM 96 NEC, 250-95 SHOULD BE 250-122. |
| |
| 10)NOTE: PLEASE SEE ALL ROOM DESIGNATION |
| -S ARE MISSING ON FLOOR PLAN? PLEASE |
| SHOW. |
| |
| 11)NOTE: PLEASE MOVE SDIN GUESTHOUSE, |
| TO BE IN IMEDIATE VICINITY OF STAIRS |
| LEADING TO SECOND FLOOR. NFPA-72 |
| 2-5.2.1.6 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |