2003-12-08 00:00:00DENIED:
 BEDROOM #3 - SUPPLY DUCT INDICATED TO
 THE BEDROOM AS 4" 25 CFM?
  
 BEDROOM #4 - SUPPLY DUCT TO INDICATES
 9" AND RETURN IS ONLY 8" 2001 FBC(M)
 601.4, RETURN SHALL BE EQUAL TO SUPPLY.
  
 PLEASE CORRECT & RE-SUBMIT.
  