Plan Review Notes For Permit 03020550 |
Permit Number |
03020550 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-10 00:00:00 | PASSED/PROVISO | | | | 1100 CU. FT. REQUIRED FOR DRYER ROOM. | | 497 CU. FT. PROVIDED @ 9'4" CEILING. | | CONFINED SPACE - TWO OPENINGS REQUIRED | | MINIMUM OF 100 SQ. IN. EACH PER SEC | | 304.3.1 |
|