Plan Review Notes For Permit 03020498 |
Permit Number |
03020498 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-02-14 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1-AREA CALCULATIONS ARE INCORRECT REVISE | | SHEET C-1 AND A-1 AS REQUIRED. | | 2-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS OR APPLY FOR SEPARATE PERMIT. | | 3-NEED RECORDED NOTICE OF COMMENCEMENT. | | 4-GARAGE DOOR STRUCTURAL BUCK DETAIL: | | SPECIFY ANCHOR EMBEDMENT AND WASHER | | SIZE. SEC. 104.2.1.2 CITY AMENDMENTS | | TO FBC. | | 5-BUILDING SECTION A/A-5: REVISE HEIGHT | | OF HANDRAIL. SEE SEC. 1007.5.1 FBC. |
|